Under Excitation Limiters

 

Description

This component represents a standard IEEE-type Under Excitation Limiter (UEL) model. All input parameters are specified either in seconds (for time constants) or in per-unit/per-unit per second (for all other inputs). The external inputs and outputs are detailed below:

 

Inputs:

Outputs:

More:

Under Excitation Limiter Model

Under Excitation Limiter Transfer Functions

PSCAD Reference [39]

Input Parameters

ConfigurationConfiguration

 

 Name for Identification

 

Text

 

Optional text parameter for identification of the component.






 UEL Type?

 

Choice

 

Select None, UEL1, or UEL2C as described in Under Excitation Limiter Transfer Functions.

 

 

 

 

 

 Summation or Takeover?


Choice


Select either Summation or Takeover mode. 






 Exc. Sys. Stabilizer Output Available?


Choice


Select either Yes or No.






 Is the Exciter ST7C?


Choice


Select either Yes or No.


This option is available when UEL Type? | UEL1 or UEL2C is selected.






UEL Status: 0-Initialize;1-Release

 

INTEGER

Variable

A variable name can be used. This variable controls the status of the UEL component.


This option is available when UEL Type? | UEL2C is selected.

 

UEL1 DataUEL1 Data

NOTE: This category is enabled only when UEL Type? | UEL1 is selected.

UEL Excitation System Stabilizer Gain [KUF]


REAL

Constant

Enter a value for the UEL excitation system stabilizer gain [pu].


This value is available when Exc. Sys. Stabilizer Output Available? | Yes is selected.






UEL Radius Setting [KUR]


REAL

Constant

Enter a value for the UEL radius setting [pu].






Upper Limit for y1 [VURmax]


REAL

Constant

Enter a value for the upper limit for y1 [pu].






UEL Center Setting [KUC]


REAL

Constant

Enter a value for the UEL center setting [pu].






Upper Limit for y2 [VUCmax]


REAL

Constant

Enter a value for the upper limit for y2 [pu].

 

UEL1 PI ControllerUEL1 PI Controller

NOTE:  This category is enabled only when UEL Type? | UEL1 is selected.

 UEL Proportional Gain [KUL]

 

REAL

Constant

Enter a value for the UEL proportional gain [pu].

 

 

 

 

 

UEL Integral Gain [KUI]

 

REAL

 Constant

Enter a value for the UEL integral gain [pu/s].

 

 

 

 

 

UEL PI Control Maximum Output [VUImax]

 

REAL

Constant

Enter a value for the UEL PI control maximum output [pu].

 

 

 

 

 

UEL PI Control Minimum Output [VUImin]

 

REAL

Constant

Enter a value for the UEL PI control minimum output [pu].

 

UEL1 CompensatorsUEL1 Compensators

NOTE:  This category is enabled only when UEL Type? | UEL1 is selected.

 UEL Numerator (Lead) Time Constant - 1st Block [TU1]

 

REAL

Constant

Enter a value for the UEL numerator (lead) time constant of the first lead/lag block [s].

 

 

 

 

 

UEL Denominator (Lag) Time Constant - 1st Block [TU2]

 

REAL

 Constant

Enter a value for the UEL denominator (lag) time constant of the first lead/lag block [s].

 

 

 

 

 

UEL Numerator (Lead) Time Constant - 2nd Block [TU3]

 

REAL

Constant

Enter a value for the UEL numerator (lead) time constant of the second lead/lag block [s].

 

 

 

 

 

UEL Denominator (Lag) Time Constant - 2nd Block [TU4]

 

REAL

Constant

Enter a value for the UEL denominator (lag) time constant of the second lead/lag block [s].

 

UEL1 OutputUEL1 Output

NOTE:  This category is enabled only when UEL Type? | UEL1 is selected.

 UEL Maximum Output [VUELmax]

 

REAL

Constant

Enter a value for the UEL maximum output [pu].

 

 

 

 

 

UEL Minimum Output [VUELmin]

 

REAL

 Constant

Enter a value for the UEL minimum output [pu].

 

UEL2C DataUEL2C Data

NOTE: This category is enabled only when UEL Type? | UEL2C is selected.

UEL Excitation System Stabilizer Gain [KUF]


REAL

Constant

Enter a value for the UEL excitation system stabilizer gain [pu].


This value is available when Exc. Sys. Stabilizer Output Available? | Yes is selected.






UEL VFB Signal Filter Gain [KFB]


REAL

Constant

Enter a value for the UEL VFB signal filter gain [pu].


This value is available when Is the Exciter ST7C? | Yes is selected.






UEL VFB Signal Filter Time Constant [TUL]


REAL

Constant

Enter a value for the UEL VFB signal filter time constant [s].


This value is available when Is the Exciter ST7C? | Yes is selected.






UEL Real Power Filter Time Constant [TUP]


REAL

Constant

Enter a value for the UEL real power filter time constant [s].






Voltage Exponent for Real Power Input to UEL Table [K1]


Choice


Select from 0, 1 or 2.






UEL Reactive Power Filter Time Constant [TUQ]


REAL

Constant

Enter a value for the UEL reactive power filter time constant [s].






Voltage Exponent for Reactive Power Output of UEL Table [K2]


Choice


Select from 0, 1 or 2.






UEL Reactive Power Reference Time Constant [TQref]


REAL

Constant

Enter a value for the UEL reactive power reference time constant [s].






UEL Voltage Filter Time Constant [TUV]


REAL

Constant

Enter a value for the UEL voltage filter time constant [s].






UEL Voltage Bias [Vbias]


REAL

Constant

Enter a value for the UEL voltage bias [pu].






UEL Logic Switch for Adjustable Gain [SW1]


Choice


Select from Pos. A (Fixed) or Pos. B (Adjustable).






UEL Fixed Gain Reduction Factor [Kfix]


REAL

Constant

Enter a value for the UEL fixed gain reduction factor [pu].






Machine Q-axis Reactance [Xq]


REAL

Constant

Enter a value for the machine Q-axis reactance [pu].


This value is available when UEL Logic Switch for Adjustable Gain | Pos. B (Adjustable) is selected.






UEL Adjustable Gain Reduction Time Constant [Tadj]


REAL

Constant

Enter a value for the UEL adjustable gain reduction time constant [s].


This value is available when UEL Logic Switch for Adjustable Gain | Pos. B (Adjustable) is selected.

 

UEL2C PI ControllerUEL2C PI Controller

NOTE:  This category is enabled only when UEL Type? | UEL2C is selected.

 UEL Proportional Gain [KUL]

 

REAL

Constant

Enter a value for the UEL proportional gain [pu].

 

 

 

 

 

UEL Integral Gain [KUI]

 

REAL

 Constant

Enter a value for the UEL integral gain [pu/s].

 

 

 

 

 

UEL PI Control Maximum Output [VUImax]

 

REAL

Constant

Enter a value for the UEL PI control maximum output [pu].

 

 

 

 

 

UEL PI Control Minimum Output [VUImin]

 

REAL

Constant

Enter a value for the UEL PI control minimum output [pu].

 

UEL1 CompensatorsUEL1 Compensators

NOTE:  This category is enabled only when UEL Type? | UEL2C is selected.

 UEL Numerator (Lead) Time Constant - 1st Block [TU1]

 

REAL

Constant

Enter a value for the UEL numerator (lead) time constant of the first lead/lag block [s].

 

 

 

 

 

UEL Denominator (Lag) Time Constant - 1st Block [TU2]

 

REAL

 Constant

Enter a value for the UEL denominator (lag) time constant of the first lead/lag block [s].

 

 

 

 

 

UEL Maximum Output - 1st Block [VUELmax2]

 

REAL

Constant

Enter a value for the UEL maximum output of the first lead/lag block [pu].

 

 

 

 

 

UEL Minimum Output - 1st Block [VUELmin2]

 

REAL

Constant

Enter a value for the UEL minimum output of the first lead/lag block [pu].






UEL Numerator (Lead) Time Constant - 2nd Block [TU3]


REAL

Constant

Enter a value for the UEL numerator (lead) time constant of the second lead/lag block [s].






UEL Denominator (Lag) Time Constant - 2nd Block [TU4]


REAL

Constant

Enter a value for the UEL denominator (lag) time constant of the second lead/lag block [s].






UEL Maximum Output - 2nd Block [VUELmax1]


REAL

Constant

Enter a value for the UEL maximum output of the second lead/lag block [pu].






UEL Minimum Output - 2nd Block [VUELmin1]


REAL

Constant

Enter a value for the UEL minimum output of the second lead/lag block [pu].

 

UEL2C Lookup TableUEL2C Lookup Table

NOTE:  This category is enabled only when UEL Type? | UEL2C is selected.

 Number of Segments in Limiting Characteristics

 

Choice


Select from 1-6.

 

 

 

 

 

UEL Lookup Table Real Power - [P#]

 

REAL

 Constant

Enter a value for the real power value corresponding to the specified point in the UEL lookup table [pu].






UEL Lookup Table Reactive Power - [Q#]


REAL

 Constant

Enter a value for the reactive power value corresponding to the specified point in the UEL lookup table [pu].