Static Exciters (2016)

 

Description

This component models a set of IEEE Standard 421.5-2016 static exciter models. Models included are ST1C, ST2C, ST3C, ST4C, ST5C, ST6C, ST7C, ST8C, ST9C and ST10C. According to the standard, ST1A, ST2A, ST3A, AC4B, ST5B, ST6B and ST7B, introduced in the older revisions of the standard, may be replaced with the newer models (with appropriate new parameter selection, which are included in the new component).

 

The models provide a continuous DC current for the synchronous machine field winding, using closed-loop control to maintain its terminal voltage. A DC generator-called exciter supplies such current based on solid-state components. The main theories behind this model are introduced in IEEE Standard 421.5-2016.

 

The main objectives of an excitation system based on its application are as follows:

Connection Port Assignments

 

More:

Exciter Models

Static Exciter Transfer Functions (2016)

Load Compensation

Synchronous Machine

IEEE Standard 421.5-2016

PSCAD References [4] and [5]

Input Parameters

ConfigurationConfiguration

 

 Name

 

Text

 

Optional text parameter for identification of the component.






 Static Exciter Type

 

Choice

 

Select ST1C, ST2C, ST3C, ST4C, ST5C, ST6C, ST7C, ST8C, ST9C or ST10C as described in Static Exciter Transfer Functions (2016).

 

 

 

 

 

Exciter Status => 0-Initialize;1-Normal

 

INTEGER

Variable

A variable name can be used.  This variable can come from Output Variables for Controller Initialization section of the Synchronous Machine input parameters

 

 

 

 

 

Output Internally Computed Initial Vref?

 

Choice

 

Select Yes or No

 

 

 

 

 

Load Compensating Resistance (Rc)

 

REAL

Constant

Enter the load compensating resistance.  See Load Compensation for more details [pu]

 

 

 

 

 

Load Compensating Reactance (Xc)

 

REAL

Constant

Enter the load compensating reactance.  See Load Compensation for more details [pu]

 

 

 

 

 

Transducer Time Constant (Tr)

 

REAL

Constant

Enter the transducer time constant.  See Load Compensation for more details [s]

 

 

 

 

 

Is There a Stabilizer?

 

Choice

 

Select Yes or No

 

Excitation LimitersExcitation Limiters

 

Under Excitation Limit Input Signal?

 

Choice

 

Select None, Summation, Take-Over (Regulator Input) or Take-Over (Inner-Loop Output).






 Over Excitation Limit Input Signal?

 

Choice

 

Select None, Summation, Take-Over (Regulator Input) or Take-Over (Inner-Loop Output).






Stator Current Limiter Input Signal?

 

Choice

 

Select None, Summation, Take-Over (Regulator Input) or Take-Over (Inner-Loop Output).






Under Excitation Stator Current Limiter Take-Over Location


Choice


Select Regulator Input or Inner-loop Output.






Over Excitation Stator Current Limiter Take-Over Location

 

Choice

 

Select Regulator Input or Inner-loop Output.






Under Excitation Limiter Input [VUEL]

 

REAL

Variable

[pu].






Over Excitation Limiter Input [VOEL]

 

REAL

Variable

[pu].






Stator Current Limiter Input at Summation (VSCLsum)


REAL

Variable

[pu].






Stator Current Limiter Input [VSCLu]

 

REAL

Variable

[pu].






Stator Current Limiter Input [VSCLo]

 

REAL

Variable

[pu].

 

ST1C: Forward Lead-Lag ParametersST1C: Forward Lead-Lag Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Stabilizer Input Signal?

 

Choice

 

Select On Regulator or On Exciter.






1st Lead Time Constant [TC]

 

REAL

Constant

[s].






1st Lag Time Constant [TB]

 

REAL

Constant

[s].






2nd Lead Time Constant [TC1]

 

REAL

Constant

[s].






2nd Lag Time Constant [TB1]

 

REAL

Constant

[s].

 

ST1C: Feedback and Regulator ParametersST1C: Feedback and Regulator Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Rate Feedback Gain [KF]

 

REAL

Constant

[pu].






Rate Feedback Time Constant [TF]

 

REAL

Constant

[s].






Regulator Gain [KA]

 

REAL

Constant

[pu].






Regulator Time Constant [TA]

 

REAL

Constant

[s].






Maximum Regulator Output [VAMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VAMIN]

 

REAL

Constant

[pu].

 

ST1C: Field Circuit ConstantsST1C: Field Circuit Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Exciter Output Current Limit Reference [ILR]

 

REAL

Constant

[pu].






Exciter Output Current Limit Gain [KLR]

 

REAL

Constant

[pu].






Maximum Field Voltage [VRMAX]

 

REAL

Constant

[pu].






Minimum Field Voltage [VRMIN]

 

REAL

Constant

[pu].






Exciter Voltage Supply

 

Choice

 

Select Bus Fed or Independent






Field Current Commutating Impedance [KC]

 

REAL

Constant

[pu].






Upper Limit on Error Signal [VIMAX]

 

REAL

Constant

[pu].






Lower Limit on Error Signal [VIMIN]

 

REAL

Constant

[pu].

 

ST2C: Feedback and Regulator ParametersST2C: Feedback and Regulator Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Rate Feedback Gain [KF]

 

REAL

Constant

[pu].






Rate Feedback Time Constant [TF]

 

REAL

Constant

[s].






Regulator Gain [KA]

 

REAL

Constant

[pu].






Regulator Time Constant [TA]

 

REAL

Constant

[s].






Maximum Regulator Output [VAMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VAMIN]

 

REAL

Constant

[pu].






Voltage Regulator  Proportional Gain [KPR]

 

REAL

Constant

[pu].






Voltage Regulator  Integral Gain [KIR]

 

REAL

Constant

[pu/s].






Maximum PI Output [VPIMAX]

 

REAL

Constant

[pu].






Minimum PI Output [VPIMIN]

 

REAL

Constant

[pu].

 

ST2C: Exciter and Compounding ParametersST2C: Exciter and Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Exciter Time Constant [TE]

 

REAL

Constant

[s].






Exciter Constant Related to Field [KE]

 

REAL

Constant

[pu].






Max Exciter Output Voltage [EFDMAX]

 

REAL

Constant

[pu].






Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].






Compounding Circuit Current. Multiplier [KI]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC]

 

REAL

Constant

[pu].






Reactance Associated with Potential Source [XL]

 

REAL

Constant

[pu].






Potential Circuit Phase Angle [ThetaP]

 

REAL

Constant

[deg].






Maximum Available Exciter Voltage [VBMAX]

 

REAL

Constant

[pu].

 

ST3C: Forward and Regulator ParametersST3C: Forward and Regulator Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Upper Limit on Error Signal

[VIMAX]

 

REAL

Constant

[pu].






Lower Limit on Error Signal [VIMIN]

 

REAL

Constant

[pu].






Voltage Regulator Proportional Gain [KPR]

 

REAL

Constant

[pu].






Voltage Regulator  

Integral Gain [KIR]

 

REAL

Constant

[pu/s].






Maximum PI Output [VPIMAX]

 

REAL

Constant

[pu].






Minimum PI Output [VPIMIN]

 

REAL

Constant

[pu].






Lead Time Constant [TC]

 

REAL

Constant

[s].






Lag Time Constant [TB]

 

REAL

Constant

[s].






Regulator Gain [KA]

 

REAL

Constant

[pu].






Regulator Time Constant [TA]

 

REAL

Constant

[s].






Maximum Regulator Output [VRMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VRMIN]

 

REAL

Constant

[pu].

 

ST3C: Inner Loop Field RegulatorST3C: Inner Loop Field Regulator

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Field Inner Loop Time Constant [TM]

 

REAL

Constant

[s].






Field Inner Loop Gain Constant [KM]

 

REAL

Constant

[pu].






Field Inner Loop Maximum Output [VMMAX]

 

REAL

Constant

[pu].






Field Inner Loop Minimum Output [VMMIN]

 

REAL

Constant

[pu].






Field Inner Loop Feedback Gain [KG]

 

REAL

Constant

[pu].






Field Inner Loop Feedback Maximum [VGMAX]

 

REAL

Constant

[pu].






Maximum Exciter Output Voltage [EFDMAX]

 

REAL

Constant

[pu].

 

ST3C: Compounding ParametersST3C: Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Magnitude of Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].






Angle of Compounding Circuit Voltage Multiplier [ThetaP]

 

REAL

Constant

[deg].






Potential Source Reactance [XL]

 

REAL

Constant

[pu].






Compounding Circuit Current Multiplier [KI]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC]

 

REAL

Constant

[pu].






Maximum Available Exciter Voltage [VBMAX]

 

REAL

Constant

[pu].






Power Source Selector 1 [SW1]

 

Choice

 

Select A or B.

 

ST4C: Regulator ConstantsST4C: Regulator Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Stabilizer Input Signal?

 

Choice

 

Select Before Take-over or After Take-over.






Regulator Proportional Gain [KPR]

 

REAL

Constant

[pu].






Regulator Integral Gain [KIR]

 

REAL

Constant

[pu].






Maximum Regulator Output [VRMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VRMIN]

 

REAL

Constant

[pu].

 

ST4C: Inner Loop Field RegulatorST4C: Inner Loop Field Regulator

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Inner Loop Proportional Gain [KPM]

 

REAL

Constant

[pu].






 Inner Loop Integral Gain [KIM]

 

REAL

Constant

[pu].






Field Inner Loop Max Output [VMMAX]

 

REAL

Constant

[pu].






Field Inner Loop Min Output [VMMIN]

 

REAL

Constant

[pu].






Regulator Time Constant [TA]

 

REAL

Constant

[s].






Maximum Exciter Output [VAMAX]

 

REAL

Constant

[pu].






Minimum Exciter Output [VAMIN]

 

REAL

Constant

[pu].






Field Inner Loop Feedback Gain [KG]

 

REAL

Constant

[pu].






Field Inner Loop Feedback Time Constant [TG]

 

REAL

Constant

[s].






Maximum Field Inner Loop Feedback Voltage [VGMAX]

 

REAL

Constant

[s].

 

ST4C: Compounding ParametersST4C: Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Power Source Selector 1? [SW1]

 

Choice

 

Select A or B.






 Magnitude of Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].






Angle of Compounding Circuit Voltage Multiplier [ThetaP]

 

REAL

Constant

[deg].






Potential Source Reactance [XL]

 

REAL

Constant

[pu].






Compounding Circuit Current Multiplier [KI]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC]

 

REAL

Constant

[pu].






Maximum Exciter Available Voltage [VBMAX]

 

REAL

Constant

[pu].

 

ST5C: Forward Lead-Lag ParametersST5C: Forward Lead-Lag Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

1st Lead Time Constant [TC1]

 

REAL

Constant

[s].






1st Lag Time Constant [TB1]

 

REAL

Constant

[s].






2nd Lead Time Constant [TC2]

 

REAL

Constant

[s].






2nd Lag Time Constant [TB2]

 

REAL

Constant

[s].






Underexcitation: 1st Lead Time Constant [TUC1]

 

REAL

Constant

[s].






Underexcitation: 1st Lag Time Constant [TUB1]

 

REAL

Constant

[s].






Underexcitation: 2nd Lead Time Constant [TUC2]

 

REAL

Constant

[s].






Underexcitation: 2nd Lag Time Constant [TUB2]

 

REAL

Constant

[s].






Overexcitation: 1st Lead Time Constant [TOC1]

 

REAL

Constant

[s].






Overexcitation: 1st Lag Time Constant [TOB1]

 

REAL

Constant

[s].






Overexcitation: 2nd Lead Time Constant [TOC2]

 

REAL

Constant

[s].






Overexcitation: 2nd Lag Time Constant [TOB2]

 

REAL

Constant

[s].






Regulator Gain [KR]

 

REAL

Constant

[pu].






Regulator Time Constant [T1]

 

REAL

Constant

[s].

 

ST5C: Field Circuit ConstantsST5C: Field Circuit Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Maximum Field Voltage [VRMAX]

 

REAL

Constant

[pu].






Minimum Field Voltage [VRMIN]

 

REAL

Constant

[pu].






Exciter Voltage Supply

 

Choice

 

Select Bus Fed or Independent






Field Current Commutating Impedance [KC]

 

REAL

Constant

[pu].

 

ST6C: Regulator ConstantsST6C: Regulator Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Regulator Proportional Gain [KPA]

 

REAL

Constant

[pu].






Regulator Integral Gain [KIA]

 

REAL

Constant

[pu].






Maximum Regulator Output [VRMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VRMIN]

 

REAL

Constant

[pu].

 

ST6C: Inner Loop Field RegulatorST6C: Inner Loop Field Regulator

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Field Inner Loop Maximum Output [VRMAX]

 

REAL

Constant

[pu].






Field Inner Loop Minimum Output [VRMIN]

 

REAL

Constant

[pu].






Field Inner Loop Feedback Gain [KG]

 

REAL

Constant

[pu].






Field Inner Loop Time Constant [TG]

 

REAL

Constant

[s].






Pre-control Gain Constant [KFF]

 

REAL

Constant

[pu].






Forward Gain Constant [KM]

 

REAL

Constant

[pu].






Current Limit Ref. [ILR]

 

REAL

Constant

[pu].






Current Limit Adjustment [KCI]

 

REAL

Constant

[pu].






Current Limit Gain [KLR]

 

REAL

Constant

[pu].






Thyristor Bridge Equivalent Time Constant [TA]

 

REAL

Constant

[s].






Rectifier Maximum Output [VMMAX]

 

REAL

Constant

[pu].






Rectifier Minimum Output [VMMIN]

 

REAL

Constant

[pu].

 

ST6C: Compounding ParametersST6C: Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 

Power Source Selector 1? [SW1]

 

Choice

 

Select A or B.






 Magnitude of Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].






Angle of Compounding Circuit Voltage Multiplier [ThetaP]

 

REAL

Constant

[deg].






Potential Source Reactance [XL]

 

REAL

Constant

[pu].






Compounding Circuit Current Multiplier [KI]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC]

 

REAL

Constant

[pu].






Maximum Exciter Available Voltage [VBMAX]

 

REAL

Constant

[pu].

 

ST7C: Regulator ConstantsST7C: Regulator Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Regulator Proportional Gain [KPA]

 

REAL

Constant

[pu].






Maximum Voltage Output [VMAX]

 

REAL

Constant

[pu].






Minimum Voltage Output [VMIN]

 

REAL

Constant

[pu].






Lead Time Constant [TC]

 

REAL

Constant

[s].






Lag Time Constant [TB]

 

REAL

Constant

[s].






Maximum Regulator Output [VRMAX]

 

REAL

Constant

[pu].






Minimum Regulator Output [VRMIN]

 

REAL

Constant

[pu].

 

ST7C: Other ParametersST7C: Other Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Exciter Lead Time Constant [TG]

 

REAL

Constant

[s].






Exciter Lag Time Constant [TF]

 

REAL

Constant

[s].






Low Band Gain [KL]

 

REAL

Constant

[pu].






High Band Gain [KH]

 

REAL

Constant

[pu].






Feedback Gain [KIA]

 

REAL

Constant

[pu].






Feedback Time Constant [TIA]

 

REAL

Constant

[s].






Thyristor Bridge Equivalent Time Constant [TA]

 

REAL

Constant

[s].






Name for VFB Signal

 

Text

 

Enter a name for the VFB signal.

 

ST8C: Regulator ConstantsST8C: Regulator Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Voltage Regulator Proportional Gain [KPR]

 

REAL

Constant

[pu].






Voltage Regulator Integral Gain [KIR]

 

REAL

Constant

[pu/s].






Maximum Voltage Regulator Output [VPIMAX]

 

REAL

Constant

[pu].






Minimum Voltage Regulator Output [VPIMIN]

 

REAL

Constant

[pu].






Field Current Regulator Proportional Gain [KPA]

 

REAL

Constant

[pu].






Field Current Regulator Integral Gain [KIA]

 

REAL

Constant

[pu/s].






Maximum Field Current Regulator Output [VAMAX]

 

REAL

Constant

[pu].






Minimum Field Current Regulator Output [VAMIN]

 

REAL

Constant

[pu].






Rectifier Bridge Equivalent Proportional Gain [KA]


REAL

Constant

[s].






Rectifier Bridge Equivalent Time Constant [TA]

 

REAL

Constant

[s].






Maximum Rectifier Bridge Regulator Output [VRMAX]

 

REAL

Constant

[pu].






Minimum Rectifier Bridge Regulator Output [VRMIN]

 

REAL

Constant

[pu].

 

ST8C: Compounding ParametersST8C: Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Exciter Field Current Feedback Gain [KF]

 

REAL

Constant

[pu].






Field Current Feedback Time Constant [TF]

 

REAL

Constant

[s].






Power Source Selector 1? [SW1]

 

Choice

 

Select A or B.






 Magnitude of Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].






Angle of Compounding Circuit Voltage Multiplier [ThetaP]

 

REAL

Constant

[deg].






Potential Source Reactance [XL]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC1]

 

REAL

Constant

[pu].






Compounding Circuit Current Multiplier [KI1]

 

REAL

Constant

[pu].






Maximum Exciter Available Voltage [VBMAX1]

 

REAL

Constant

[pu].






Rectifier Loading Factor [KC2]

 

REAL

Constant

[pu].






Compounding Circuit Current Multiplier [KI2]

 

REAL

Constant

[pu].






Maximum Exciter Available Voltage [VBMAX2]

 

REAL

Constant

[pu].

 

ST9C: Feedback and Regulator ParametersST9C: Feedback and Regulator Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

 Regulator Differential Time Constant [TCD]

 

REAL

Constant

[s].

 

 

 

 

 

Regulator Differential Filter Time Constant [TBD]

 

REAL

Constant

[s].

 

 

 

 

 

 Regulator Differential Deadband [ZA]

 

REAL

Constant

[pu].

 

 

 

 

 

Regulator Gain [KA]

 

REAL

Constant

[pu].

 

 

 

 

 

UEL Takeover Activation Gain [KU]

 

REAL

Constant

[pu].

 

 

 

 

 

Regulator Time Constant [TA]

 

REAL

Constant

[s].

 

 

 

 

 

Underexcitation Limiter Time Constant [TAUEL]

 

REAL

Constant

[s].

 

 

 

 

 

Maximum Regulator Output [VAMAX]

 

REAL

Constant

[pu].

         

Minimum Regulator Output [VAMIN]

 

REAL

Constant

[pu].

 

 

 

 

 

Power Converter Gain [KAS]

 

REAL

Constant

[pu].

 

 

 

 

 

Power Converter Time Constant [TAS]

 

REAL

Constant

[s].

 

ST9C: Exciter and Compounding ParametersST9C: Exciter and Compounding Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].

 

 

 

 

 

Potential Circuit Phase Angle [ThetaP]

 

REAL

Constant

[deg].

 

 

 

 

 

Compounding Circuit Current Multiplier [KI]

 

REAL

Constant

[pu].

 

 

 

 

 

Reactance Associated with Potential Source [XL]

 

REAL

Constant

[pu].

 

 

 

 

 

Power Source Selector 1? [SW1]

 

Choice

 

Select A or B.

 

 

 

 

 

Rectifier Loading Factor [KC]

 

REAL

Constant

[pu].

 

 

 

 

 

Maximum Available Exciter Voltage [VBMAX]

 

REAL

Constant

[pu].

 

ST10C: Forward Lead-Lag ParametersST10C: Forward Lead-Lag Parameters

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Stabilizer Input Signal?

 

Choice

 

Select Voltage Error Summation, Voltage Error Takeover or AVR Output.

 

 

 

 

 

1st Lead Time Constant [TC1]

 

REAL

Constant

[s].

 

 

 

 

 

1st Lag Time Constant [TB1]

 

REAL

Constant

[s].

 

 

 

 

 

2nd Lead Time Constant [TC2]

 

REAL

Constant

[s].

 

 

 

 

 

2nd Lag Time Constant [TB2]

 

REAL

Constant

[s].

 

 

 

 

 

Underexcitation: 1st Lead Time Constant [TUC1]

 

REAL

Constant

[s].

 

 

 

 

 

Underexcitation: 1st Lag Time Constant [TUB1]

 

REAL

Constant

[s].

 

 

 

 

 

Underexcitation: 2nd Lead Time Constant [TUC2]

 

REAL

Constant

[s].

 

 

 

 

 

Underexcitation: 2nd Lag Time Constant [TUB2]

 

REAL

Constant

[s].

 

 

 

 

 

Overexcitation: 1st Lead Time Constant [TOC1]

 

REAL

Constant

[s].

 

 

 

 

 

Overexcitation: 1st Lag Time Constant [TOB1]

 

REAL

Constant

[s].

 

 

 

 

 

Overexcitation: 2nd Lead Time Constant [TOC2]

 

REAL

Constant

[s].

 

 

 

 

 

Overexcitation: 2nd Lag Time Constant [TOB2]

 

REAL

Constant

[s].

 

 

 

 

 

Regulator Gain [KR]

 

REAL

Constant

[pu].

 

 

 

 

 

Regulator Time Constant [T1]

 

REAL

Constant

[s].

 

ST10C: Field Circuit ConstantsST10C: Field Circuit Constants

NOTE:  See Static Exciter Transfer Functions (2016) for more details.

Maximum Field Voltage [VRMAX]

 

REAL

Constant

[pu].

 

 

 

 

 

Minimum Field Voltage [VRMIN]

 

REAL

Constant

[pu].

 

 

 

 

 

Maximum PSS Regulator Output [VRSMAX]

 

REAL

Constant

[pu].

         

Minimum PSS Regulator Output [VRSMIN]

 

REAL

Constant

[pu].

 

 

 

 

 

Field Current Commutating Impedance [KC]

 

REAL

Constant

[pu].

 

 

 

 

 

Power Source Selector 1 [SW1]

 

Choice

 

Select A or B.

 

 

 

 

 

Magnitude of Compounding Circuit Voltage Multiplier [KP]

 

REAL

Constant

[pu].

         

Angle of Compounding Circuit Voltage Multiplier [ThetaP]

 

REAL

Constant

[deg].

         

Compounding Circuit Current Multiplier [KI]

 

REAL

Constant

[pu].

         

 Potential Source Reactance [XL]

 

REAL

Constant

[pu].

         

Maximum Available Exciter Voltage [VBMAX]

 

REAL

Constant

[pu].

 

Internal Output VariablesInternal Output Variables

 

 Output of Excitation System Stabilizer (VF)

 

Text

 

 

 

 

 

 

 

Output VA of ST1C Exciter (VA)

 

Text