This component represents a standard IEEE-type Over Excitation Limiter (OEL) model. All input parameters are specified either in seconds (for time constants) or in per-unit/per-unit per second (for all other inputs). The external inputs and outputs are detailed below:
Inputs:
The limited quantity, input to the OEL model is user-selectable and may consist of one of the following: Generator field current (IF), generator field voltage (EF), or a signal proportional to the exciter field current (VFE) - which is typically used in applications with brush-less excitation systems. The reactive power input is supported exclusively by the OEL4C type.
EF: Generator field voltage.
VFE: Signal proportional to the exciter field current.
IF: Generator field current.
Q: Generator reactive power.
Outputs:
VOEL: This output represents the calculated Over Excitation Limiter (OEL) signal, which is typically used in conjunction with an exciter model.
|
More: |
Over Excitation Limiter Transfer Functions PSCAD References [39] |
|
Name for Identification |
Text |
Optional text parameter for identification of the component. |
||
|
|
|
|
|
|
|
OEL Type? |
|
Choice |
|
Select None, OEL2C, OEL3C, OEL4C, or OEL5C as described in Over Excitation Limiter Transfer Functions. |
|
|
|
|
|
|
|
Summation or Takeover? |
|
Choice |
|
Select either Summation or Takeover mode. The available options for each mode are as follows:
|
|
|
|
|
|
|
|
OEL Status: 0-Initialize;1-Release |
|
INTEGER |
Variable |
A variable name can be used. This variable controls the status of the OEL component. |
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Input |
|
Choice |
|
Select from None, Field Current (IF), Generator Field Voltage (EF), or Exciter Field Current (VFE), based on your requirement. |
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Input Signal Scaling Factor [KSCALE] |
|
REAL |
Constant |
Enter a value for the OEL input signal scaling factor [pu]. |
|
|
|
|
|
|
|
OEL Input Signal Filter Time Constant [TRoel] |
|
REAL |
Constant |
Enter a value for the OEL input signal filter time constant [s]. |
|
|
|
|
|
|
|
OEL Reference for Inverse Time Calculations [ITFpu] |
|
REAL |
Constant |
Enter a value for the OEL reference for inverse time calculations [pu]. |
|
|
|
|
|
|
|
OEL Actual Value Scaling Factor [Kact] |
|
REAL |
Constant |
Enter a value for the OEL actual value scaling factor [pu]. |
OEL2C Timer LogicOEL2C Timer Logic
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Gain for Calculation of IERRinv2 [K2] |
|
REAL |
Constant |
Enter a value for the OEL gain for calculation of IERRinv2 [pu]. |
|
|
|
|
|
|
|
OEL Exponent for Calculation of IERRinv2 [c2] |
|
REAL |
Constant |
Enter a value for the OEL exponent for calculation of IERRinv2 [pu]. |
|
|
|
|
|
|
|
OEL Maximum Inverse Time Output [VINVmax] |
|
REAL |
Constant |
Enter a value for the OEL maximum inverse time output [pu]. |
|
|
|
|
|
|
|
OEL Minimum Inverse Time Output [VINVmin] |
|
REAL |
Constant |
Enter a value for the OEL minimum inverse time output [pu]. |
|
|
|
|
|
|
|
OEL Fixed Delay Time Output [Fixedru] |
|
REAL |
Constant |
Enter a value for the OEL fixed delay time output [pu]. |
|
|
|
|
|
|
|
OEL Fixed Cooling-down Time Output [Fixedrd] |
|
REAL |
Constant |
Enter a value for the OEL fixed cooling-down time output [pu]. |
OEL2C Ramp Rate LogicOEL2C Ramp Rate Logic
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Gain for Calculation of IERRinv1 [K1] |
|
REAL |
Constant |
Enter a value for the OEL gain for calculation of IERRinv1 [pu]. |
|
|
|
|
|
|
|
Ramp Rate Selector: Fixed or Function of Field Current Error? [SW1] |
|
Choice |
|
Select from Fixed or Function of Field Current Error. |
|
|
|
|
|
|
|
OEL Exponent for Calculation of IERRinv1 [c1] |
|
REAL |
Constant |
Enter a value for the OEL exponent for calculation of IERRinv1 [pu]. |
|
|
|
|
|
|
|
OEL Timer Maximum Level [Tmax] |
|
REAL |
Constant |
Enter a value for the OEL timer maximum level [pu]. |
|
|
|
|
|
|
|
OEL Timer Minimum Level [Tmin] |
|
REAL |
Constant |
Enter a value for the OEL timer minimum level [pu]. |
|
|
|
|
|
|
|
OEL Timer Feedback Gain [KFB] |
|
REAL |
Constant |
Enter a value for the OEL timer feedback gain [pu]. |
|
|
|
|
|
|
|
OEL Timer Reference [TFCL] |
|
REAL |
Constant |
Enter a value for the OEL timer reference [pu]. |
|
|
|
|
|
|
|
OEL Ramp-down Rate [Krd] |
|
REAL |
Constant |
Enter a value for the OEL ramp-down rate [pu]. |
|
|
|
|
|
|
|
OEL Ramp-up Rate [Kru] |
|
REAL |
Constant |
Enter a value for the OEL ramp-up rate [pu]. |
|
|
|
|
|
|
|
OEL Thermal Reference Release Threshold [KZRU] |
|
REAL |
Constant |
Enter a value for the OEL thermal reference release threshold [pu]. |
|
|
|
|
|
|
|
OEL Instantaneous Field Current Limit [Iinst] |
|
REAL |
Constant |
Enter a value for the OEL instantaneous field current limit [pu]. |
|
|
|
|
|
|
|
OEL Thermal Field Current Limit [Ilim] |
|
REAL |
Constant |
Enter a value for the OEL thermal field current limit [pu]. |
|
|
|
|
|
|
|
OEL Reference Filter Time Constant [TAoel] |
|
REAL |
Constant |
Enter a value for the OEL reference filter time constant [s]. |
OEL2C Activation LogicOEL2C Activation Logic
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Reset Reference, if OEL is inactive [Ireset] |
|
REAL |
Constant |
Enter a value for the OEL reset reference [pu]. |
|
|
|
|
|
|
|
OEL Activation Delay Time [Ten] |
|
REAL |
Constant |
Enter a value for the OEL activation delay time [s]. |
|
|
|
|
|
|
|
OEL Reset Delay Time [Toff] |
|
REAL |
Constant |
Enter a value for the OEL reset delay time [s]. |
|
|
|
|
|
|
|
OEL Reset Delay Threshold [ITHoff] |
|
REAL |
Constant |
Enter a value for the OEL reset delay threshold [pu]. |
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
OEL Output Compensation Type |
|
Choice |
|
Select from Gain, PID Controller, Two Lead/Lag Compensators or All. |
|
|
|
|
|
|
|
OEL PID Regulator Proportional Gain [KPoel] |
|
REAL |
Constant |
Enter a value for the OEL PID regulator proportional gain [pu]. This parameter should be set accordingly based on the compensation type. |
|
|
|
|
|
|
|
OEL PID Regulator Integral Gain [KIoel] |
|
REAL |
Constant |
Enter a value for the OEL PID regulator integral gain [pu/s].
This parameter should be set accordingly based on the compensation type. |
|
|
|
|
|
|
|
OEL PID Regulator Differential Gain [KDoel] |
|
REAL |
Constant |
Enter a value for the OEL PID regulator differential gain [s]. This value is available when OEL Output Compensation Type | PID Controller or All is selected. |
|
|
|
|
|
|
|
OEL PID Regulator Differential Time Constant [TDoel] |
|
REAL |
Constant |
Enter a value for the OEL PID regulator differential time constant [s]. This value is available when OEL Output Compensation Type | PID Controller or All is selected. |
|
|
|
|
|
|
|
Maximum OEL PID Output Limit [VOELmax3] |
|
REAL |
Constant |
Enter a value for the maximum OEL PID output limit [pu]. This value is available when OEL Output Compensation Type | PID Controller or All is selected. |
|
|
|
|
|
|
|
Minimum OEL PID Output Limit [VOELmin3] |
|
REAL |
Constant |
Enter a value for the minimum OEL PID output limit [pu]. This value is available when OEL Output Compensation Type | PID Controller or All is selected. |
|
|
|
|
|
|
|
OEL Regulator Numerator (Lead) Time Constant 2 [TC2oel] |
|
REAL |
Constant |
Enter a value for the OEL regulator numerator (lead) time constant 2 [s]. This value is available when OEL Output Compensation Type | PID Controller or All is selected. |
|
|
|
|
|
|
|
OEL Regulator Denominator (Lag) Time Constant 2 [TB2oel] |
|
REAL |
Constant |
Enter a value for the OEL regulator denominator (lag) time constant 2 [s]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
Maximum OEL Lead-lag 1 Output Limit [VOELmax2] |
|
REAL |
Constant |
Enter a value for the maximum OEL lead-lag 1 output limit [pu]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
Minimum OEL Lead-lag 1 Output Limit [VOELmin2] |
|
REAL |
Constant |
Enter a value for the minimum OEL lead-lag 1 output limit [pu]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
OEL Regulator Numerator (Lead) Time Constant 1 [TC1oel] |
|
REAL |
Constant |
Enter a value for the OEL regulator numerator (lead) time constant 1 [s]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
OEL Regulator Denominator (Lag) Time Constant 1 [TB1oel] |
|
REAL |
Constant |
Enter a value for the OEL regulator denominator (lag) time constant 1 [s]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
Maximum OEL Output Limit [VOELmax1] |
|
REAL |
Constant |
Enter a value for the maximum OEL output limit [pu]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
|
|
|
|
|
|
|
Minimum OEL Output Limit [VOELmin1] |
|
REAL |
Constant |
Enter a value for the minimum OEL output limit [pu]. This value is available when OEL Output Compensation Type| Two Lead/Lag Compensators or All is selected. |
NOTE: This category is enabled only when OEL Type? | OEL3C is selected.
|
OEL Input |
|
Choice |
|
Select from None, Field Current (IF), Generator Field Voltage (EF), or Exciter Field Current (VFE), based on your requirement. |
NOTE: This category is enabled only when OEL Type? | OEL3C is selected.
|
OEL Timed Field Current Limiter Pickup Level [ITFpu] |
|
REAL |
Constant |
Enter a value for the OEL timed field current limiter pickup level [pu]. |
|
|
|
|
|
|
|
OEL Input Signal Scaling Factor [KSCALE] |
|
REAL |
Constant |
Enter a value for the OEL input signal scaling factor [pu]. |
|
|
|
|
|
|
|
OEL Field Current Measurement Time Constant [TF] |
|
REAL |
Constant |
Enter a value for the OEL field current measurement time constant [s]. |
|
|
|
|
|
|
|
Exponent for OEL Error Calculation [K1] |
|
Choice |
|
Select from Linear or Quadratic. |
|
|
|
|
|
|
|
OEL Gain [KOEL] |
|
REAL |
Constant |
Enter a value for the OEL gain [pu]. |
OEL3C PI ControllerOEL3C PI Controller
NOTE: This category is enabled only when OEL Type? | OEL3C is selected.
|
OEL Proportional Gain [KPOEL] |
|
REAL |
Constant |
Enter a value for the OEL proportional gain [pu]. |
|
|
|
|
|
|
|
OEL Integral Time Constant [TOEL] |
|
REAL |
Constant |
Enter a value for the OEL integral time constant [s]. |
|
|
|
|
|
|
|
OEL Integrator Maximum Output [VOELmax1] |
|
REAL |
Constant |
Enter a value for the OEL integrator maximum output [pu]. |
|
|
|
|
|
|
|
OEL Integrator Minimum Output [VOELmin1] |
|
REAL |
Constant |
Enter a value for the OEL integrator minimum output [pu]. |
NOTE: This category is enabled only when OEL Type? | OEL3C is selected.
|
OEL Maximum Output [VOELmax2] |
|
REAL |
Constant |
Enter a value for the OEL maximum output [pu]. |
|
|
|
|
|
|
|
ROEL Minimum Output [VOELmin2] |
|
REAL |
Constant |
Enter a value for the OEL minimum output [pu]. |
NOTE: This category is enabled only when OEL Type? | OEL4C is selected.
|
OEL Timed Reactive Power Limiter Pickup Level [QREF] |
|
REAL |
Constant |
Enter a value for the OEL timed reactive power limiter pickup level [pu]. |
|
|
|
|
|
|
|
OEL Fixed Time Delay [Tdelay] |
|
REAL |
Constant |
Enter a value for the OEL fixed time delay [s]. |
OEL4C PI ControllerOEL4C PI Controller
NOTE: This category is enabled only when OEL Type? | OEL4C is selected.
|
OEL Proportional Gain [KP] |
|
REAL |
Constant |
Enter a value for the OEL proportional gain [pu]. |
|
|
|
|
|
|
|
OEL Integral Gain [KI] |
|
REAL |
Constant |
Enter a value for the OEL integral gain [pu/s]. |
|
|
|
|
|
|
|
OEL Minimum Output [Vmin] |
|
REAL |
Constant |
Enter a value for the OEL minimum output [pu]. |
NOTE: This category is enabled only when OEL Type? | OEL5C is selected.
|
OEL Input |
|
Choice |
|
Select from None, Field Current (IF), Generator Field Voltage (EF), or Exciter Field Current (VFE), based on your requirement. |
NOTE: This category is enabled only when OEL Type? | OEL5C is selected.
|
OEL Reference 1 [IFDref1] |
|
REAL |
Constant |
Enter a value for the OEL reference 1 [pu]. |
|
|
|
|
|
|
|
OEL Reference 2 [IFDref2] |
|
REAL |
Constant |
Enter a value for the OEL reference 2 [pu]. |
|
|
|
|
|
|
|
Scale Factor for OEL Input [KSCALE1] |
|
REAL |
Constant |
Enter a value for the scale factor for OEL input [pu]. |
|
|
|
|
|
|
|
OEL Input Transducer Time Constant [TF1] |
|
REAL |
Constant |
Enter a value for the OEL input transducer time constant [s]. |
|
|
|
|
|
|
|
OEL Lead-Lag Gain [K] |
|
REAL |
Constant |
Enter a value for the OEL lead-lag gain [pu]. |
|
|
|
|
|
|
|
OEL Lead Time Constant [TCoel] |
|
REAL |
Constant |
Enter a value for the OEL lead time constant [s]. |
|
|
|
|
|
|
|
OEL Lag Time Constant [TBoel] |
|
REAL |
Constant |
Enter a value for the OEL lag time constant [s]. |
|
|
|
|
|
|
|
OEL Proportional Gain [KPoel] |
|
REAL |
Constant |
Enter a value for the OEL proportional gain [pu]. |
|
|
|
|
|
|
|
OEL Integral Gain [KIoel] |
|
REAL |
Constant |
Enter a value for the OEL integral gain [pu/s]. |
|
|
|
|
|
|
|
OEL PI Controller Upper Limit [VOELmax] |
|
REAL |
Constant |
Enter a value for the OEL PI controller upper limit [pu]. |
|
|
|
|
|
|
|
OEL PI Controller Lower Limit [VOELmin] |
|
REAL |
Constant |
Enter a value for the OEL PI controller lower limit [pu]. |
OEL5C VFE InputOEL5C VFE Input
NOTE: This category is enabled only when OEL Type? | OEL5C is selected.
|
OEL Reference Logic Switch [SW1] |
|
Choice |
|
Select from Pos. A (Ibias) or Pos. B (VFE). |
|
|
|
|
|
|
|
OEL Reference Bias [Ibias] |
|
REAL |
Constant |
Enter a value for the OEL reference bias [pu]. |
|
|
|
|
|
|
|
Exciter Field Current Reference Setpoint [VFEref] |
|
REAL |
Constant |
Enter a value for the exciter field current reference setpoint [pu]. This value is available when OEL Reference Logic Switch | Pos. A (Ibias) is selected. |
|
|
|
|
|
|
|
Scale Factor (IFEbase/IFErated) [KSCALE2] |
|
REAL |
Constant |
Enter a value for the scale factor (IFEbase/IFErated) [pu]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
|
|
|
|
|
|
|
Exciter Field Current Transducer Time Constant [TF2] |
|
REAL |
Constant |
Enter a value for the exciter field current transducer time constant [s]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
|
|
|
|
|
|
|
Exciter Field Current Regulator Proportional Gain [KPVfe] |
|
REAL |
Constant |
Enter a value for the exciter field current regulator proportional gain [pu]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
|
|
|
|
|
|
|
Exciter Field Current Regulator Integral Gain [KIVfe] |
|
REAL |
Constant |
Enter a value for the exciter field current regulator integral gain [pu/s]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
|
|
|
|
|
|
|
Exciter Field Current Regulator Upper Limit [VVFEmax] |
|
REAL |
Constant |
Enter a value for the exciter field current regulator upper limit [pu]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
|
|
|
|
|
|
|
Exciter Field Current Regulator Lower Limit [VVFEmin] |
|
REAL |
Constant |
Enter a value for the exciter field current regulator lower limit [pu]. This value is available when OEL Reference Logic Switch | Pos. B (VFE) is selected. |
OEL2C Activation LogicOEL2C Activation Logic
NOTE: This category is enabled only when OEL Type? | OEL5C is selected.
|
OEL Activation Logic Pickup Level [IFDpulev] |
|
REAL |
Constant |
Enter a value for the OEL activation logic pickup level [pu]. |
|
|
|
|
|
|
|
OEL Activation Logic Timer Setpoint [TIFDlev] |
|
REAL |
Constant |
Enter a value for the OEL activation logic timer setpoint [s]. |
OEL5C Inverse Time FunctionOEL5C Inverse Time Function
NOTE: This category is enabled only when OEL Type? | OEL2C is selected.
|
Exponent for Inverse Time Function [K1] |
|
Choice |
Select from Linear or Quadratic. |
|
|
|
|
|
|
|
|
OEL Inverse Time Integrator Pickup Level [IFDpu] |
|
REAL |
Constant |
Enter a value for the OEL inverse time integrator pickup level [pu]. |
|
|
|
|
|
|
|
OEL Inverse Time Limit Active Level [IFDlim] |
|
REAL |
Constant |
Enter a value for the OEL inverse time limit active level [pu.s]. |
|
|
|
|
|
|
|
OEL Inverse Time Upper Limit [VOELmax1] |
|
REAL |
Constant |
Enter a value for the OEL inverse time upper limit [pu.s]. |
|
|
|
|
|
|
|
OEL Inverse Time Integrator Time Constant [TOEL] |
|
REAL |
Constant |
Enter a value for the OEL inverse time integrator time constant [s]. |
|
|
|
|
|
|
|
OEL Inverse Time Leak Gain [KIFDT] |
|
REAL |
Constant |
Enter a value for the OEL inverse time leak gain [pu]. |