Universal Tower

 

Description

PSCAD contains a variety of pre-constructed Overhead Line Towers.  The tower components are used to define the geometric configuration of the transmission line system within the The TLine/Cable Configuration Editor.  The Universal Tower component is a special transmission line tower that allows the user to enter conductor geometric data in X, Y coordinates, instead of in terms of conductor spacing.

 

Note that if conductors are grouped into circuits via the Grouping parameter, the load flow RXB data will be displayed in the output file for 6, 9 and 12 conductor towers.

 

More:

Constructing Overhead Lines

Transmission Lines and Cables

Input Parameters

 

Graphic of conductor sag is

 

Choice

 

Select visible or hidden.  Selecting visible will display the conductor sag graphic on the tower component:

 

 

 

 

 

 

Ideal transposition of this circuit is

 

Choice

 

Select enabled or disabled.  Selecting enabled will assume ideally transposed conductors in the calculation of the line constants.  See Conductor Transposition for more details.

 

 

 

 

 

Shunt conductance

 

REAL

Literal

Enter the shunt conductance of the transmission line [S/m].

 

 

 

 

 

 Name

 

Text

 

Enter a descriptive name for the tower, such as the actual tower number from your system

 

 

 

 

 

Total Number of Conductors

 

Choice

 

Enter the total number of conductors, excluding ground wires (maximum 12).

 

 

 

 

 

Tower/Conductor/

Ground Wire Placement

(Varies with Tower)

 

REAL

Literal

Enter the geometric spacing data for the tower, conductors and ground wires as per the individual tower components [m].

 

NOTE:  If conductor X, Y coordinate data entry is preferred, see the Universal Tower

 

Conductor DataConductor Data

 

Data entry method

 

Choice

 

Select from library file or direct.  See Using/Maintaining a Conductor Library for more information on using conductor libraries.

 

 

 

 

 

Path to conductor library file

 

Text

 

Enter the absolute path to a conductor library file.  See Using/Maintaining a Conductor Library for more details.

 

This parameter is only enabled if Data entry method | from library file is selected.

 

 

 

 

 

Conductor style is

 

Choice

 

Select solid core, hollow or stranded type.

 

 

 

 

 

Grouping

 

Choice

 

Enable grouping  if you would like to organize the conductors them into circuits.

 

This is important for the display of double-circuit line constants in load flow RXB format in the output file.

 

This parameter is enabled only if Total Number of Conductors is set to 6, 9 or 12, and Ideal Transposition is enabled.

 

 

 

 

 

Name

 

Text

 

Enter a descriptive name for the conductor type.  Only one conductor type per tower is allowed.

 

 

 

 

 

Outer radius

 

REAL

Literal

Enter the outer radius of the conductor assembly. If stranded, then this value is the radius from the centre to the edge of the outer strands [m].

 

When bundled conductors exist (i.e. Total bundled sub-conductors > 1), this value is the individual outer radius of each sub-conductor in the bundle.

 

This parameter is only enabled if Data entry method | direct is selected.

 

 

 

 

 

Inner radius

 

REAL

Literal

Enter the inner radius of the conductor assembly [m]. Must be less than the outer radius.

 

This parameter is only enabled if Path to conductor library file | hollow is selected.

 

 

 

 

 

Strand radius

 

REAL

Literal

Enter the radius of a single conductor strand [m].

 

This parameter is only enabled if Path to conductor library file | stranded is selected.

 

 

 

 

 

Total Number of Strands

 

INTEGER

Literal

Enter the total number of strands that make up the  entire conductor.

 

 

 

 

 

Total Number of Outer Strands

 

INTEGER

Literal

Enter the total number of strands that line the circumference of the conductor assembly only (not the total number of strands for the entire conductor).

 

 

 

 

 

DC resistance (entire conductor)

 

REAL

Literal

Enter the DC resistance of the entire conductor assembly (i.e. all strands included if stranded) [W/km].  

 

When bundled conductors exist (i.e. Total bundled sub-conductors > 1), this value is the individual DC resistance of a sub-conductor in the bundle.

 

This parameter is only enabled if Data entry method | direct is selected.

 

 

 

 

 

Relative permeability

 

REAL

Literal

Enter the relative permeability of the conductor material.

 

 

 

 

 

Sag (all conductors)

 

REAL

Literal

Enter the sag for all conductors. This is the difference between the height at the tower, to the height mid-span [m].

 

 

 

 

 

Total bundled sub-conductors

 

Choice

 

Select 1 to 15.

 

 

 

 

 

Bundle configuration is

 

Choice

 

Select symmetrical or asymmetrical.  If asymmetrical is selected, the X, Y coordinates of each sub-conductor must be entered in the Asymmetrical Bundling Position Data parameter page.  See The PSCAD Line Constants Program for more details.

 

 

 

 

 

Sub-conductor spacing

 

REAL

Literal

Enter the distance between sub-conductors in the bundle [m].

 

 This parameter is only enabled if Bundle configuration is | symmetrical is selected.   See The PSCAD Line Constants Program for more details.

 

 

 

 

 

Bundle graphic is

 

Choice

 

Select visible or hidden.  Selecting visible will display the bundle graphic on the tower component:

 

Conductor CoordinatesConductor Coordinates

 

 Conductor C# (X,Y)

 

REAL

Literal

Enter the geometric X, Y coordinates for each conductor in the right of way [m]

 

 

Ground Wire DataGround Wire Data

 

Total number of ground wires is

 

Choice

 

Select the number of ground wires (1 or 2) for this tower.

 

 

 

 

 

Ground wires are

 

Choice

 

Select whether or not the ground wires are identical.

 

This parameter is enabled only if Total number of ground wires is |2 is selected.

 

 

 

 

 

Ground wire elimination is

 

Choice

 

Select enabled or disabled.  If enabled is selected, the ground wires will be mathematically eliminated.

 

 

 

 

 

 Data entry method

 

Choice

 

Select from library file or direct.  See Using/Maintaining a Conductor Library for more information on using conductor libraries.

 

 

 

 

 

Path to ground wire library file

 

Text

 

Enter the absolute path to a conductor library file.  See Using/Maintaining a Conductor Library for more details.

 

This parameter is only enabled if Data entry method | from library file is selected.

 

 

 

 

 

Name

 

Text

 

Enter a descriptive name for the ground wire type.

 

 

 

 

 

Outer radius

 

REAL

Literal

Enter the outer radius of the ground wire [m].

 

This parameter is only enabled if Data entry method | direct is selected.

 

 

 

 

 

DC resistance

 

REAL

Literal

Enter the ground wire DC Resistance [W/km].  

 

This parameter is only enabled if Data entry method | direct is selected.

 

 

 

 

 

Relative permeability

 

REAL

Literal

Enter the relative permeability of the ground wire.

 

 

 

 

 

Sag (all ground wires)

 

REAL

Literal

Enter the sag for all ground wires. This is the difference between the height at the tower, to the height mid-span [m].

 

 

Ground Wire CoordinatesGround Wire Coordinates

 

 Ground Wire G# (X,Y)

 

REAL

Literal

Enter the geometric X, Y coordinates for each ground wire in the right of way [m]

 

 

Asymmetrical Bundling Position DataAsymmetrical Bundling Position Data

 

  Sub-Conductor # - X Postion

 

REAL

Literal

Enter the geometric X-coordinates for the bundled sub-conductors, about the bundle centre point [m].

 

 

 

 

 

 Sub-Conductor # - Y Postion

 

REAL

Literal

Enter the geometric Y-coordinates for the bundled sub-conductors, about the bundle centre point [m].

 

 

Phase/Node Connection InformationPhase/Node Connection Information

 

Conductor # (C#)

 

INTEGER

Literal

Enter the connection number for the corresponding tower conductor.   

 

This number will indicate to which external electrical connection on the Overhead Line Interface this conductor is to be attached