
This component models a set of IEEE Standard 421.5-2016 AC exciter models. Models included are AC1C, AC2C, AC3C, AC4C, AC5C, AC6C, AC7C, AC8C, AC9C, AC10C and AC11C. According to the standard, AC1A, AC2A, AC3A, AC4A, AC5A, AC6A, AC7B and AC8B, introduced in the older revisions of the standard, may be replaced with the newer models (with appropriate new parameter selection, which are included in the new component).
The models provide a continuous DC current for the synchronous machine field winding, using closed-loop control to maintain its terminal voltage. An AC generator-called exciter supplies such current through rectifiers, brushes, and slip rings. The main theories behind this model are introduced in IEEE Standard 421.5-2016.
The main objectives of an excitation system based on its application are as follows:
Constant terminal voltage: Helps the synchronous generator to maintain its terminal voltage at desirable level.
Constant power factor: Helps the synchronous motor to maintain its power factor at desirable level.
Connection Port Assignments
Ef: Outputs the calculated field voltage to be applied directly to the synchronous machine in per-unit.
Vref0: Outputs the initialised value of the reference voltage (Vref) in per-unit. It is visible only if the input parameter Output Internally Computed Initial Vref? is selected as Yes.
Ef0: Imports the synchronous machine field voltage during the initialisation period in per-unit.
VI/IT: Imports the synchronous machine RMS terminal voltage, real terminal current and imaginary terminal current in a 3-element array format.
Vref: Imports the desired voltage reference for the synchronous machine terminal in per-unit.
VS: Imports the generated signal by power system stabiliser in per-unit.
If: Imports the synchronous machine field current in per-unit.
|
More: |
|
Name |
Text |
Optional text parameter for identification of the component. |
||
|
|
|
|
|
|
|
AC Exciter Type |
|
Choice |
|
Select AC1C, AC2C, AC3C, AC4C, AC5C, AC6C, AC7 , AC8C, AC9C, AC10C or AC11C, as described in AC Exciter Transfer Functions (2016). |
|
|
|
|
|
|
|
Exciter Status => 0-Initialize;1-Normal |
|
INTEGER |
Variable |
A variable name can be used. This variable can come from Output Variables for Controller Initialization section of the Synchronous Machine input parameters. |
|
|
|
|
|
|
|
Output Internally Computed Initial Vref? |
|
Choice |
|
Select Yes or No.
Selecting Yes will add a connection port for outputting Vref0. |
|
|
|
|
|
|
|
Load Compensating Resistance [Rc] |
|
REAL |
Constant |
Enter the load compensating resistance. See Load Compensation for more details [pu]. |
|
|
|
|
|
|
|
Load Compensating Reactance (Xc) |
|
REAL |
Constant |
Enter the load compensating reactance. See Load Compensation for more details [pu]. |
|
|
|
|
|
|
|
Transducer Time Constant (Tr) |
|
REAL |
Constant |
Enter the transducer time constant. See Load Compensation for more details [s]. |
|
|
|
|
|
|
|
Is There a Stabilizer? |
|
Choice |
|
Select Yes or No.
Selecting Yes will add a connection port for importing VS. |
AC Rotating Exciter ParametersAC Rotating Exciter Parameters
|
Exciter Field Current Upper Limit [VFEMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Exciter Voltage Output [VEMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Time Constant [TE] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Constant Related to Field [KE] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Circuit Commutating Reactance [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Demagnetizing Factor [KD] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Saturation at VE1 [SE(VE1)] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Voltage for SE1 [VE1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Saturation at VE2 [SE(VE2)] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Voltage for SE2 [VE2] |
|
REAL |
Constant |
[pu]. |
Excitation LimitersExcitation Limiters
|
Under Excitation Limit Input Signal? |
Choice |
Select None, Summation Point or Take-over. |
||
|
|
||||
|
Over Excitation Limit Input Signal? |
|
Choice |
|
Select None, Summation Point or Take-over. |
|
|
|
|
|
|
|
Over Excitation Stator Current Limiter Signal? |
|
Choice |
|
Select None or Take-over. |
|
|
|
|
|
|
|
Under Excitation Limiter Input [VUEL] |
|
REAL |
Variable |
[pu]. |
|
Over Excitation Limiter Input [VOEL] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
|
|
Stator Current Limiter Input at Summation [VSCLsum] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
|
|
Under Excitation Stator Current Limiter Input at Take-Over [VSCLu] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
|
|
Over Excitation Stator Current Limiter Input at Take-Over [VSCLo] |
|
REAL |
Variable |
[pu]. |
AC1C: Forward Path ParametersAC1C: Forward Path Parameters
|
Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Exciter Field Voltage [EFMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Exciter Field Voltage [EFMIN] |
|
REAL |
Constant |
[pu]. |
AC1C: Feedback ParametersAC1C: Feedback Parameters
|
Rate Feedback Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rate Feedback Time Constant [TF] |
|
REAL |
Constant |
[s]. |
AC2C: Forward Path ParametersAC2C: Forward Path Parameters
|
Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Second Stage Regulator Gain [KB] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Exciter Field Voltage [EFEMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Exciter Field Voltage [EFEMIN] |
|
REAL |
Constant |
[pu]. |
AC2C: Feedback ParametersAC2C: Feedback Parameters
|
Include Fast Feedback Loops? |
|
Choice |
|
Select Yes or No. |
|
|
|
|
|
|
|
Rate Feedback Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rate Feedback Time Constant [TF] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Field Current Feedback Gain [KH] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Gain [KL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLR] |
|
REAL |
Constant |
|
AC3C: Forward Path ParametersAC3C: Forward Path Parameters
|
Regulator Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Integral Gain [KIR] |
|
REAL |
Constant |
[pu/s]. |
|
|
|
|
|
|
|
Regulator Derivative Gain [KDR] |
|
REAL |
Constant |
[pu.s]. |
|
|
|
|
|
|
|
Regulator Derivative Time Constant [TDR] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Output [VPIDMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Output [VPIDMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator and Alternator Field Supply Constant [KR] |
|
REAL |
Constant |
[pu]. |
AC3C: Feedback ParametersAC3C: Feedback Parameters
|
Include Fast Feedback Loops? |
|
Choice |
|
Select Yes or No. |
|
|
|
|
|
|
|
Rate Feedback Gain Below EFDN [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rate Feedback Gain Above EFDN [KN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Efd Value at Which KF Changes [EFDN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rate Feedback Time Constant [TF] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Field Current Limiter Loop Gain [KFA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Field Current Limiter Time Constant [TFA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Field Current Limiter Loop Reference [ETX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Field Current Limiter Loop Proportional Gain [KL1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLV] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Gain [KLV] |
|
REAL |
Constant |
[pu]. |
AC4C: Regulator ConstantsAC4C: Regulator Constants
|
Upper Limit on Error Signal [VIMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Lower Limit on Error Signal [VIMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Regulator Integral Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC] |
|
REAL |
Constant |
[pu]. |
AC5C: Regulator ConstantsAC5C: Regulator Constants
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Output [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Output [VAMIN] |
|
REAL |
Constant |
[pu]. |
AC5C: Feedback ParametersAC5C: Feedback Parameters
|
Rate Feedback Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rate Feedback Time Constant [TF1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Feedback Lag-Time Constant [TF2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Feedback Lead-Time Constant [TF3] |
|
REAL |
Constant |
[s]. |
AC6C: Forward Path ParametersAC6C: Forward Path Parameters
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
First Lead Time Constant [TK] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
First Lag Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Second Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Second Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Regulator Output [EFEMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Regulator Output [EFEMIN] |
|
REAL |
Constant |
[pu]. |
AC6C: Feedback ParametersAC6C: Feedback Parameters
|
Exciter Field Current Reference [VFELIM] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Current Feedback Gain [KH] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Field Current Limit [VHMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Field Limiter Lag Time [TH] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Exciter Field Limiter Lead Time [TJ] |
|
REAL |
Constant |
[s]. |
AC7C: Forward Path ParametersAC7C: Forward Path Parameters
|
PSS Signal? |
|
Choice |
|
Select Summation point I or Summation point II.
Enabled only if Is There a Stabilizer? is selected as Yes. |
|
|
|
|
|
|
|
Regulator Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Integral Gain [KIR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Derivative Gain [KDR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Regulator Derivative Time Constant [TDR] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Regulator Output [VRMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Inner PI Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Inner PI Integral Gain [KIA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Potential Circuit Gain Coefficient [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
|
Potential Circuit Current Gain Coefficient [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Source Reactance [XL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Power Source Selector 1 [SW1] |
|
Choice |
|
Select A or B. |
|
|
|
|
|
|
|
Power Source Selector 2 [SW2] |
|
Choice |
|
Select A or B. |
|
|
|
|
|
|
|
EFD Multiplying Constant [KR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Lower Limit Multiplying Constant [KL] |
|
REAL |
Constant |
[pu]. |
AC7C: Feedback ParametersAC7C: Feedback Parameters
|
Feedback Gain [KF1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Feedback Gain [KF2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Feedback Derivative Gain [KF3] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Feedback Derivative Time Constant [TF] |
|
REAL |
Constant |
[s]. |
AC8C: Regulator ConstantsAC8C: Regulator Constants
|
PSS Signal? |
|
Choice |
|
Select Summation point I or Summation point II.
Enabled only if Is There a Stabilizer? is selected as Yes. |
|
|
|
|
|
|
|
PID Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Integral Gain [KIR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Derivative Gain [KDR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Derivative Time Constant [TDR] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum PID Output [VPIDMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum PID Output [VPIDMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Regulator Gain [KA] |
REAL |
Constant |
[pu]. |
|
|
Regulator Time Constant [TA] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Regulator Output [VRMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Potential Circuit Gain Coefficient [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
|
Potential Circuit Current Gain Coefficient [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Source Reactance [XL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Power Source Selector 1 [SW1] |
|
Choice |
|
Select A or B. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLV] |
|
REAL |
Constant |
[pu]. |
AC9C: Regulator ConstantsAC9C: Regulator Constants
|
PID Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Integral Gain [KIR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Derivative Gain [KDR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
PID Derivative Time Constant [TDR] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Maximum PID Output [VPIDMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum PID Output [VPIDMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Regulator Gain [KPA] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Regulator Integral Gain [KIA] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Regulator Output [VAMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Regulator Output [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Inner PI Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Inner PI Integral Gain [KIA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Regulator Internal Voltage [VAMAX] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Minimum Regulator Internal Voltage [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Rectifier Bridge Gain [KA] |
REAL |
Constant |
[pu]. |
|
|
Rectifier Bridge Time Constant [TA] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Rectifier Bridge Output [VRMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Rectifier Bridge Output [VRMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Free Wheel Feedback Gain [KFW] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Free Wheel Feedback Output [VFWMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Minimum Free Wheel Feedback Output [VFWMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Power Stage Type? |
|
Choice |
|
Select Chopper or Thyristor. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Circuit Gain Coefficient [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Potential Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX1] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Rectifier Loading Factor [KC2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI2] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Power Source Selector [SW1] |
|
Choice |
|
Select A or B. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLV] |
|
REAL |
Constant |
[pu]. |
AC9C: Feedback ParametersAC9C: Feedback Parameters
|
Feedback Loop Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Feedback Loop Time Constant [TF] |
|
REAL |
Constant |
[s]. |
AC10C: Regulator ConstantsAC10C: Regulator Constants
|
PSS Signal? |
Choice |
Select None, a, b or c.
Enabled only if Is There a Stabilizer? is selected as Yes. |
||
|
|
|
|
|
|
|
Regulator Gain [KR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Voltage Regulator Lag Time Constant [TB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
Voltage Regulator Lead Time Constant [TC1] |
REAL |
Constant |
[s]. |
|
|
Voltage Regulator Lag Time Constant [TB2] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Voltage Regulator Lead Time Constant [TC2] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
UEL Regulator Lag Time Constant [TUB1] |
REAL |
Constant |
[s]. |
|
|
UEL Regulator Lead Time Constant [TUC1] |
REAL |
Constant |
[s]. |
|
|
UEL Regulator Lag Time Constant [TUB2] |
REAL |
Constant |
[s]. |
|
|
UEL Regulator Lead Time Constant [TUC2] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
OEL Regulator Lag Time Constant [TOB1] |
REAL |
Constant |
[s]. |
|
|
OEL Regulator Lead Time Constant [TOC1] |
REAL |
Constant |
[s]. |
|
|
OEL Regulator Lag Time Constant [TOB2] |
REAL |
Constant |
[s]. |
|
|
OEL Regulator Lead Time Constant [TOC2] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Maximum PSS Regulator Output [VRSMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum PSS Regulator Output [VRSMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Regulator Output [VRMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Exciter Field Current Regulator Feedback Selector? |
Choice |
|
Select A and B. |
|
|
|
|
|
|
|
|
Exciter Field Current Regulator Time Constant [TEXC] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Exciter Field Current Regulator Feedback Gain [KEXC] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Exciter Field Current Regulator Proportional Gain [KCR] |
REAL |
Constant |
[pu]. |
|
|
Exciter Field Current Regulator Lead Time Constant [TF1] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Exciter Field Current Regulator Lag Time Constant [TF2] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Exciter Field Current Limiter Feedback Gain [KVFE] |
REAL |
Constant |
[pu]. |
|
|
Exciter Field Current Limiter Proportional Gain [KLIM] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Power Source Selector [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
|
|
Potential Circuit Gain Coefficient [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Potential Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC1] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX1] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI2] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Rectifier Loading Factor [KC2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLV] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Field Current Limiter Reference [VFELIM] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Exciter Constant Related to Field [KE] |
|
REAL |
Constant |
[pu]. |
AC11C: Regulator ConstantsAC11C: Regulator Constants
|
PSS Signal? |
Choice |
Select None, a, b or c.
Enabled only if Is There a Stabilizer? is selected as Yes. |
||
|
|
|
|
|
|
|
Voltage Regulator Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Voltage Regulator Integral Time Constant [TIA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
UEL Regulator Proportional Gain [KPU] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
UEL Regulator Integral Time Constant [TIU] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
OEL Regulator Proportional Gain [KPO] |
REAL |
Constant |
[pu]. |
|
|
OEL Regulator Integral Time Constant [TIO] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
|
|
Maximum PSS Regulator Output [VRSMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum PSS Regulator Output [VRSMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Regulator Output [VRMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Exciter Output [VAMAX] |
REAL |
Constant |
[pu]. |
|
|
Minimum Exciter Output [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Power Source Selector [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
|
|
Potential Circuit Gain Coefficient [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI1] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Potential Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
|
Rectifier Loading Factor [KC1] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX1] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Compound Circuit Gain Coefficient [KI2] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
|
Rectifier Loading Factor [KC2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Maximum Available Field Voltage [VBMAX2] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Additive Independent Source [KBOOST] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Reference Value for Additive Independent Source Application [VBOOST] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
|
Field Limiter Loop Reference [VLV] |
|
REAL |
Constant |
[pu]. |
Internal Output VariablesInternal Output Variables
|
Name: Output of Excitation System Stabilizer [VF] |
Text |
|||
|
|
|
|
|
|
|
Excitor Field Current [VFE] |
|
Text |
|