This component models a voltage dependent voltage order characteristic for the HVDC Combined Coordinated Control Method (CCCM). CCCM combines and coordinates the DC current and DC voltage control at each DC station.
More: |
Inverter ParametersInverter Parameters
NOTE: See CCCM Controllers for more details.
Name for Identification |
Text |
Optional text parameter for identification of the component. |
||
Maximum Current Capability |
|
REAL |
Variable |
This input is usually 1.0 or greater. It should be the maximum level at which the HVDC link can maintain a steady state current [pu] |
|
|
|
|
|
Voltage above which VDCOL is Off |
|
REAL |
Variable |
Whenever DC voltage Udi rises to this level or greater, there is no voltage dependent current order limit applied. Can use the same setting as the rectifier [pu] |
|
|
|
|
|
Minimum Current Limit |
|
REAL |
Variable |
The minimum current order limit for the inverter. Use the same setting as the rectifier [pu] |
|
|
|
|
|
Voltage when VDCOL is Fully On |
|
REAL |
Variable |
The voltage setting entered here defines the level of DC voltage below which the minimum current level is maintained. Use the same setting as the rectifier [pu] |