
This component models a set of IEEE Standard 421.5-2016 static exciter models. Models included are ST1C, ST2C, ST3C, ST4C, ST5C, ST6C, ST7C, ST8C, ST9C and ST10C. According to the standard, ST1A, ST2A, ST3A, AC4B, ST5B, ST6B and ST7B, introduced in the older revisions of the standard, may be replaced with the newer models (with appropriate new parameter selection, which are included in the new component).
The models provide a continuous DC current for the synchronous machine field winding, using closed-loop control to maintain its terminal voltage. A DC generator-called exciter supplies such current based on solid-state components. The main theories behind this model are introduced in IEEE Standard 421.5-2016.
The main objectives of an excitation system based on its application are as follows:
Constant terminal voltage: Helps the synchronous generator to maintain its terminal voltage at desirable level.
Constant power factor: Helps the synchronous motor to maintain its power factor at desirable level.
Connection Port Assignments
Ef: Outputs the calculated field voltage to be applied directly to the synchronous machine in per-unit.
Vref0: Outputs the initialized value of the reference voltage (Vref) in per-unit. It is visible only if the input parameter Output Internally Computed Initial Vref? is selected as Yes.
Ef0: Imports the synchronous machine field voltage during the initialization period in per-unit.
VI/IT: Imports the synchronous machine RMS terminal voltage, real terminal current and imaginary terminal current in a 3-element array format.
Vref: Imports the desired voltage reference for the synchronous machine terminal in per-unit.
VS: Imports the generated signal by power system stabilizer in per-unit.
If: Imports the synchronous machine field current in per-unit.
More: |
Name |
Text |
Optional text parameter for identification of the component. |
||
Static Exciter Type |
|
Choice |
|
Select ST1C, ST2C, ST3C, ST4C, ST5C, ST6C, ST7C, ST8C, ST9C or ST10C as described in Static Exciter Transfer Functions (2016). |
|
|
|
|
|
Exciter Status => 0-Initialize;1-Normal |
|
INTEGER |
Variable |
A variable name can be used. This variable can come from Output Variables for Controller Initialization section of the Synchronous Machine input parameters |
|
|
|
|
|
Output Internally Computed Initial Vref? |
|
Choice |
|
Select Yes or No |
|
|
|
|
|
Load Compensating Resistance (Rc) |
|
REAL |
Constant |
Enter the load compensating resistance. See Load Compensation for more details [pu] |
|
|
|
|
|
Load Compensating Reactance (Xc) |
|
REAL |
Constant |
Enter the load compensating reactance. See Load Compensation for more details [pu] |
|
|
|
|
|
Transducer Time Constant (Tr) |
|
REAL |
Constant |
Enter the transducer time constant. See Load Compensation for more details [s] |
|
|
|
|
|
Is There a Stabilizer? |
|
Choice |
|
Select Yes or No |
Under Excitation Limit Input Signal? |
Choice |
Select None, Summation, Regulator Input or Inner-loop Output. |
||
|
||||
Over Excitation Limit Input Signal? |
|
Choice |
|
Select None, Summation, Regulator Input or Inner-loop Output. |
|
|
|
|
|
Under Excitation Stator Current Limiter Signal? |
|
Choice |
|
Select None, Summation, Regulator Input or Inner-loop Output. |
|
|
|
|
|
Over Excitation Stator Current Limiter Signal? |
|
Choice |
|
Select None, Regulator Input or Inner-loop Output. |
|
|
|
|
|
Under Excitation Limiter Input [VUEL] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
Over Excitation Limiter Input [VOEL] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
Stator Current Limiter Input [VSCLu] |
|
REAL |
Variable |
[pu]. |
|
|
|
|
|
Stator Current Limiter Input [VSCLo] |
|
REAL |
Variable |
[pu]. |
ST1C: Forward Lead-Lag Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Stabilizer Input Signal? |
|
Choice |
|
Select On Regulator or On Exciter. |
|
|
|
|
|
1st Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
1st Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lead Time Constant [TC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lag Time Constant [TB1] |
|
REAL |
Constant |
[s]. |
ST1C: Feedback and Regulator Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Rate Feedback Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rate Feedback Time Constant [TF] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Maximum Regulator Output [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Regulator Output [VAMIN] |
|
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Exciter Output Current Limit Reference [ILR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Exciter Output Current Limit Gain [KLR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Field Voltage [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Field Voltage [VRMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Exciter Voltage Supply |
|
Choice |
|
Select Bus Fed or Independent |
|
|
|
|
|
Field Current Commutating Impedance [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Upper Limit on Error Signal [VIMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Lower Limit on Error Signal [VIMIN] |
|
REAL |
Constant |
[pu]. |
ST2C: Feedback and Regulator Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Rate Feedback Gain [KF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rate Feedback Time Constant [TF] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Maximum Regulator Output [VAMAX] |
REAL |
Constant |
[pu]. |
|
Minimum Regulator Output [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Voltage Regulator Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Voltage Regulator Integral Gain [KIR] |
|
REAL |
Constant |
[pu/s]. |
|
|
|
|
|
Maximum PI Output [VPIMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum PI Output [VPIMIN] |
|
REAL |
Constant |
[pu]. |
ST2C: Exciter and Compounding Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Exciter Time Constant [TE] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Exciter Constant Related to Field [KE] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Max Exciter Output Voltage [EFDMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Compounding Circuit Voltage Multiplier [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Compounding Circuit Current. Multiplier [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rectifier Loading Factor [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Reactance Associated with Potential Source [XL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Potential Circuit Phase Angle [ThetaP] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
Maximum Available Exciter Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
ST3C: Forward and Regulator Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Upper Limit on Error Signal [VIMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Lower Limit on Error Signal [VIMIN] |
|
REAL |
Constant |
[pu]. |
Voltage Regulator Proportional Gain [KPR] |
REAL |
Constant |
[pu]. |
|
Voltage Regulator Integral Gain [KIR] |
REAL |
Constant |
[pu/s]. |
|
Maximum PI Output [VPIMAX] |
REAL |
Constant |
[pu]. |
|
Minimum PI Output [VPIMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Lead Time Constant [TC] |
REAL |
Constant |
[s]. |
|
Lag Time Constant [TB] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
ST3C: Inner Loop Field Regulator
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Field Inner Loop Time Constant [TM] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Field Inner Loop Gain Constant [KM] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Maximum Output [VMMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Minimum Output [VMMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Feedback Gain [KG] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Feedback Maximum [VGMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Exciter Output Voltage [EFDMAX] |
|
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Magnitude of Compounding Circuit Voltage Multiplier [|KP|] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Angle of Compounding Circuit Voltage Multiplier [THETA_p] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
Potential Source Reactance [XL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Compounding Circuit Current Multiplier [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rectifier Loading Factor [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Available Exciter Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Stabilizer Input Signal? |
|
Choice |
|
Select Before Take-over or After Take-over. |
|
|
|
|
|
Regulator Proportional Gain [KPR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Integral Gain [KIR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
ST4C: Inner Loop Field Regulator
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Inner Loop Proportional Gain [KPM] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Inner Loop Integral Gain [KIM] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Max Output [VMMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Min Output [VMMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [TA] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Maximum Exciter Output [VAMAX] |
REAL |
Constant |
[pu]. |
|
Minimum Exciter Output [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Field Inner Loop Feedback Gain [KG] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Feedback Time Constant [TG] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Maximum Field Inner Loop Feedback Voltage [VGMAX] |
REAL |
Constant |
[s]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
Magnitude of Compounding Circuit Voltage Multiplier [|KP|] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Angle of Compounding Circuit Voltage Multiplier [THETA_p] |
|
REAL |
Constant |
[deg]. |
|
|
|
|
|
Potential Source Reactance [XL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Compounding Circuit Current Multiplier [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rectifier Loading Factor [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Exciter Available Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
ST5C: Forward Lead-Lag Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
1st Lead Time Constant [TC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
1st Lag Time Constant [TB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lead Time Constant [TC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lag Time Constant [TB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 1st Lead Time Constant [TUC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 1st Lag Time Constant [TUB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 2nd Lead Time Constant [TUC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 2nd Lag Time Constant [TUB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 1st Lead Time Constant [TOC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 1st Lag Time Constant [TOB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 2nd Lead Time Constant [TOC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 2nd Lag Time Constant [TOB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Gain [KR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [T1] |
|
REAL |
Constant |
[s]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Maximum Field Voltage [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Field Voltage [VRMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Exciter Voltage Supply |
|
Choice |
|
Select Bus Fed or Independent |
|
|
|
|
|
Field Current Commutating Impedance [KC] |
|
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Regulator Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Integral Gain [KIA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
ST6C: Inner Loop Field Regulator
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Field Inner Loop Maximum Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Minimum Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Feedback Gain [KG] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Inner Loop Time Constant [TG] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Pre-control Gain Constant [KFF] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Forward Gain Constant [KM] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Current Limit Ref. [ILR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Current Limit Adjustment [KCI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Current Limit Gain [KLR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Thyristor Bridge Equivalent Time Constant [TA] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Rectifier Maximum Output [VMMAX] |
REAL |
Constant |
[pu]. |
|
Rectifier Minimum Output [VMMIN] |
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
Magnitude of Compounding Circuit Voltage Multiplier [|KP|] |
REAL |
Constant |
[pu]. |
|
Angle of Compounding Circuit Voltage Multiplier [THETA] |
REAL |
Constant |
[deg]. |
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
Compounding Circuit Current Multiplier [KI] |
REAL |
Constant |
[pu]. |
|
Rectifier Loading Factor [KC] |
REAL |
Constant |
[pu]. |
|
Maximum Exciter Available Voltage [VBMAX] |
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Regulator Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Voltage Output [VMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Voltage Output [VMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Lead Time Constant [TC] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Lag Time Constant [TB] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Maximum Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Exciter Lead Time Constant [TG] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Exciter Lag Time Constant [TF] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Low Band Gain [KL] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
High Band Gain [KH] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Feedback Gain [KIA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Feedback Time Constant [TIA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Thyristor Bridge Equivalent Time Constant [TA] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Name for VFB Signal |
|
Text |
|
Enter a name for the VFB signal. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Voltage Regulator Proportional Gain [KPR] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Voltage Regulator Integral Gain [KIR] |
REAL |
Constant |
[pu/s]. |
|
|
|
|
|
|
Maximum Voltage Regulator Output [VPIMAX] |
REAL |
Constant |
[pu]. |
|
Minimum Voltage Regulator Output [VPIMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Field Current Regulator Proportional Gain [KPA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Field Current Regulator Integral Gain [KIA] |
REAL |
Constant |
[pu/s]. |
|
|
|
|
|
|
Maximum Field Current Regulator Output [VAMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Field Current Regulator Output [VAMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Rectifier Equivalent Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Maximum Rectifier Bridge Regulator Output [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Rectifier Bridge Regulator Output [VRMIN] |
|
REAL |
Constant |
[pu]. |
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Exciter Field Current Feedback Gain [KF] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Field Current Feedback Time Constant [TF] |
REAL |
Constant |
[s]. |
|
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
Magnitude of Compounding Circuit Voltage Multiplier [|KP|] |
REAL |
Constant |
[pu]. |
|
Angle of Compounding Circuit Voltage Multiplier [THETA] |
REAL |
Constant |
[deg]. |
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
Rectifier Loading Factor [KC1] |
REAL |
Constant |
[pu]. |
|
Compounding Circuit Current Multiplier [KI1] |
REAL |
Constant |
[pu]. |
|
Maximum Exciter Available Voltage [VBMAX1] |
REAL |
Constant |
[pu]. |
|
Rectifier Loading Factor [KC2] |
REAL |
Constant |
[pu]. |
|
Compounding Circuit Current Multiplier [KI2] |
REAL |
Constant |
[pu]. |
|
Maximum Exciter Available Voltage [VBMAX2] |
REAL |
Constant |
[pu]. |
ST9C: Feedback and Regulator Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Regulator Differential Time Constant [TCD] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Differential Filter Time Constant [TBD] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Differential Deadband [ZA] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Regulator Gain [KA] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
UEL Takeover Activation Gain [KU] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Regulator Time Constant [TA] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation Limiter Time Constant [TAUEL] |
REAL |
Constant |
[s]. |
|
|
|
|
|
|
Maximum Regulator Output [VAMAX] |
REAL |
Constant |
[pu]. |
|
Minimum Regulator Output [VAMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Power Converter Gain [KAS] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Power Converter Time Constant [TAS] |
|
REAL |
Constant |
[s]. |
ST9C: Exciter and Compounding Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Compounding Circuit Voltage Multiplier [KP] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Potential Circuit Phase Angle [ThetaP] |
REAL |
Constant |
[deg]. |
|
|
|
|
|
|
Compounding Circuit Current Multiplier [KI] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Reactance Associated with Potential Source [XL] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
Rectifier Loading Factor [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum Available Exciter Voltage [VBMAX] |
|
REAL |
Constant |
[pu]. |
ST10C: Forward Lead-Lag Parameters
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Stabilizer Input Signal? |
Choice |
Select Voltage Error Summation, Voltage Error Takeover or AVR Output. |
||
|
|
|
|
|
1st Lead Time Constant [TC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
1st Lag Time Constant [TB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lead Time Constant [TC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
2nd Lag Time Constant [TB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 1st Lead Time Constant [TUC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 1st Lag Time Constant [TUB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 2nd Lead Time Constant [TUC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Underexcitation: 2nd Lag Time Constant [TUB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 1st Lead Time Constant [TOC1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 1st Lag Time Constant [TOB1] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 2nd Lead Time Constant [TOC2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Overexcitation: 2nd Lag Time Constant [TOB2] |
|
REAL |
Constant |
[s]. |
|
|
|
|
|
Regulator Gain [KR] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Regulator Time Constant [T1] |
|
REAL |
Constant |
[s]. |
ST10C: Field Circuit Constants
NOTE: See Static Exciter Transfer Functions (2016) for more details.
Maximum Field Voltage [VRMAX] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Minimum Field Voltage [VRMIN] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Maximum PSS Regulator Output [VRSMAX] |
REAL |
Constant |
[pu]. |
|
Minimum PSS Regulator Output [VRSMIN] |
REAL |
Constant |
[pu]. |
|
|
|
|
|
|
Field Current Commutating Impedance [KC] |
|
REAL |
Constant |
[pu]. |
|
|
|
|
|
Power Source Selector 1 [SW1] |
Choice |
Select A or B. |
||
|
|
|
|
|
Magnitude of Compounding Circuit Voltage Multiplier [|KP|] |
REAL |
Constant |
[pu]. |
|
Angle of Compounding Circuit Voltage Multiplier [THETA] |
REAL |
Constant |
[deg]. |
|
Compounding Circuit Current Multiplier [KI] |
REAL |
Constant |
[pu]. |
|
Potential Source Reactance [XL] |
REAL |
Constant |
[pu]. |
|
Maximum Available Exciter Voltage [VBMAX] |
REAL |
Constant |
[pu]. |