Power System Stabilizers (2016)

 

Description

This component models IEEE-type, power system stabilizers.  

 

The inputs to this model are per-unit speed w, synchronous machine terminal voltage Vt, and discontinuous controller reference Vk.  The output is Vs, which can be speed, terminal frequency, power or none.

 

More:

Power System Stabilizer Models

 

Stabilizer Transfer Functions (2016)

PSCAD References [39]

Input Parameters

ConfigurationConfiguration

 

 Name for Identification

 

Text

 

Optional text parameter for identification of the component.

 

 

 

 

 

 PSS Status: 0-Initialize; 1-Release

 

INTEGER

Variable

A variable name can be used. This variable controls the status of the PSS.

 

 

 

 

 

DEC Status: 0-Initialize; 1-Release

 

INTEGER

Variable

A variable name can be used. This variable controls the status of the DEC.

 

 

 

 

 

Stabilizer?

 

Choice

 

Select from None, PSS1A, PSS2C, PSS3C, PSS4C, PSS5C, PSS6C or PSS7C. 

 

 

 

 

 

Discontinuous Excitation Controller?

 

Choice

 

Select None, DEC1A, DEC2A, or DEC3A.

 

PSS1A: Power System Stabilizer DataPSS1A: Power System Stabilizer Data

NOTE:  This category is enabled only when Stabilizer? | PSS1A is selected.

 Input Signal

 

Choice

 

Select None, Frequency, Speed or Power






Transducer Time Constant [T6]

 

REAL

Constant

Enter a value for the transducer time constant [s].






PSS gain [Ks]

 

REAL

Constant

Enter a value for the PSS gain [pu].






Washout Time Constant [T5]

 

REAL

Constant

Enter a value for the washout time constant [s].






Filter Constant [A1]

 

REAL

Constant

Enter a value for the filter constant.






Filter Constant [A2]

 

REAL

Constant

Enter a value for the filter constant.






First Lead Time Constant [T1]

 

REAL

Constant

Enter a value for the 1st lead time constant [s].






First Lag Time Constant [T2]

 

REAL

Constant

Enter a value for the 1st lag time constant [s].






Second Lead Time Constant [T3]

 

REAL

Constant

Enter a value for the 2nd lead time constant [s].






Second Lag Time Constant [T4]

 

REAL

Constant

Enter a value for the 2nd lag time constant [s].






PSS Output Max. Limit [VSTMAX]

 

REAL

Constant

Enter a value for the PSS output maximum limit [pu].






PSS Output Min. Limit [VSTMIN]

 

REAL

Constant

Enter a value for the PSS output minimum limit [pu].

 

PSS2C: PSS Signal DataPSS2C: PSS Signal Data

NOTE:  This category is enabled only when Stabilizer? | PSS2C is selected.

 First Input Signal

 

Choice

 

Select None, Frequency, Speed or Power.






First Signal Maximum Input [VSI1MAX]

 

REAL

Constant

Enter a value for the first signal maximum input [pu].






First Signal Minimum Input [VSI1MIN]

 

REAL

Constant

Enter a value for the first signal minimum input [pu].






1st Signal 1st Washout Time [TW1]

 

REAL

Constant

Enter a value for the first signal first washout time [s].






1st Signal 2nd Washout Time [TW2]

 

REAL

Constant

Enter a value for the first signal second washout time [s].






1st Signal Transducer Time Constant [T6]

 

REAL

Constant

Enter a value for the first signal transducer time constant [s].






Second Input Signal

 

Choice

 

Select None, Frequency, Speed or Power.






Second Signal Maximum Input [VSI2MAX]

 

REAL

Constant

Enter a value for the second signal maximum input [pu].






Second Signal Minimum Input [VSI2MIN]

 

REAL

Constant

Enter a value for the second signal minimum input [pu].






2nd Signal 1st Washout Time [TW3]

 

REAL

Constant

Enter a value for the second signal first washout time [s].






2nd Signal 2nd Washout Time [TW4]

 

REAL

Constant

Enter a value for the second signal second washout time [s].






2nd Signal Gain [Ks2]

 

REAL

Constant

Enter a value for the second signal gain [pu].






2nd Signal Transducer Time Const. [T7]

 

REAL

Constant

Enter a value for the second signal transducer time constant [s].






2nd Signal 2nd Gain [Ks3]

 

REAL

Constant

Enter a value for the second signal second gain [pu].

 

PSS2C: PSS Lead-Lag DataPSS2C: PSS Lead-Lag Data

NOTE:  This category is enabled only when Stabilizer? | PSS2C is selected.

 Filter Lead Time constant [T8]

 

REAL

Constant

Enter a value for the filter lead time constant [s].






Filter Lag Time constant [T9]

 

REAL

Constant

Enter a value for the filter lag time constant [s].






Integer Filter Constant [N]

 

INTEGER

Constant

Enter a value for the integer filter constant.






Integer Filter Constant [M]

 

INTEGER

Constant

Enter a value for the integer filter constant.






PSS Gain [Ks1]

 

REAL

Constant

Enter a value for the PSS gain [pu].






1st Lead Time Constant [T1]

 

REAL

Constant

Enter a value for the 1st lead time constant [s].






1st Lag Time Constant [T2]

 

REAL

Constant

Enter a value for the 1st lag time constant [s].






2nd Lead Time Constant [T3]

 

REAL

Constant

Enter a value for the 2nd lead time constant [s].






2nd Lag Time Constant [T4]

 

REAL

Constant

Enter a value for the 2nd lag time constant [s].






3rd Lead Time Constant [T10]

 

REAL

Constant

Enter a value for the 3rd lead time constant [s].






3rd Lag Time Constant [T11]

 

REAL

Constant

Enter a value for the 3rd lag time constant [s].






4th Lead Time Constant [T12]


REAL

Constant

Enter a value for the 4th lead time constant [s].






4th Lag Time Constant [T13]


REAL

Constant

Enter a value for the 4th lag time constant [s].






PSS Output Maximum Limit [VSTMAX]

 

REAL

Constant

Enter a value for the PSS output maximum limit [pu].






PSS Output Minimum Limit [VSTMIN]

 

REAL

Constant

Enter a value for the PSS output minimum limit [pu].






PSS Output Logic - Upper Threshold for Power Output [PPSON]


REAL

Constant

Enter a value for the PSS output logic - upper threshold for power output [pu].






PSS Output Logic - Lower Threshold for Power Output [PPSOFF]


REAL

Constant

Enter a value for the PSS output logic - lower threshold for power output [pu].

 

PSS3C: Power System Stabilizer DataPSS3C: Power System Stabilizer Data

NOTE:  This category is enabled only when Stabilizer? | PSS3C is selected.

 First Input Signal

 

Choice

 

Select None, Frequency, Speed or Power

First Transducer Time Constant [T1]

 

REAL

Constant

Enter a value for the first transducer time constant [s].

First Signal Washout Time Constant [Tw1]

 

REAL

Constant

Enter a value for the first signal washout time constant [s].

First Input Signal Gain [Ks1]

 

REAL

Constant

Enter a value for the first input signal gain [pu].

Second Input Signal

 

Choice

 

Select None, Frequency, Speed or Power

Second Transducer Time Constant [T2]

 

REAL

Constant

Enter a value for the second transducer time constant [s].

Second Signal Washout Time Constant [Tw2]

 

REAL

Constant

Enter a value for the second signal washout time constant [s].

Second Input Signal Gain [Ks2]

 

REAL

Constant

Enter a value for the second input signal gain [pu].

 

PSS3C: Power System Stabilizer Data: Common PathPSS3C: Power System Stabilizer Data: Common Path

NOTE:  This category is enabled only when Stabilizer? | PSS3C is selected.

Washout Time Constant [Tw3]

 

REAL

Constant

Enter a value for the washout time constant [s].

Filter Coefficient [A#]

 

REAL

Constant

Enter a value for the corresponding filter coefficients [s].

PSS Output Maximum Limit [VSTMAX]

 

REAL

Constant

Enter a value for the PSS output maximum limit [pu].

PSS Output Minimum Limit [VSTMIN]

 

REAL

Constant

Enter a value for the PSS output minimum limit [pu].

PSS Output Logic - Upper Threshold for Power Output [PPSON]


REAL

Constant

Enter a value for the PSS output logic - upper threshold for power output [pu].

PSS Output Logic - Lower Threshold for Power Output [PPSOFF]


REAL

Constant

Enter a value for the PSS output logic - lower threshold for power output [pu].

 

PSS4C: Power System Stabilizer Data: Common DataPSS4C: Power System Stabilizer Data: Common Data

NOTE:  This category is enabled only when Stabilizer? | PSS4C is selected.

Include Notch Filters?

 

Choice

 

Select Yes or No.

Inertia Constant [H]

 

REAL

Constant

Enter a value for the inertia constant [s].

PSS Output Maximum Limit [VSTMAX]

 

REAL

Constant

Enter a value for the PSS output maximum limit [pu].

PSS Output Minimum Limit [VSTMIN]

 

REAL

Constant

Enter a value for the PSS output minimum limit [pu].

Tuned Frequency of the Notch Filter [WNI]

 

REAL

Constant

Enter a value for the tuned frequency of the notch filter [Hz].


This value is only available when Include Notch Filters? | Yes is selected.

3dB Bandwidth of the Notch Filter (BWI)

 

REAL

Constant

Enter a value for the 3dB bandwidth of the notch filter [Hz].


This value is only available when Include Notch Filters? | Yes is selected.

 

PSS4C: Power System Stabilizer Data: Very Low Frequency BandPSS4C: Power System Stabilizer Data: Very Low Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS4C is selected.

Gain in Positive Branch [KVL1]

 

REAL

Constant

Enter a value for the gain in positive branch [pu].

Proportional Gain in First Block [KVL11]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TVL1]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TVL2]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TVL3]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TVL4]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TVL5]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TVL6]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Negative Branch [KVL2]

 

REAL

Constant

Enter a value for the gain in negative branch [pu].

Proportional Gain in First Block [KVL17]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TVL7]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TVL8]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TVL9]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TVL10]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TVL11]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TVL12]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Common Branch [KVL]

 

REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VVLMAX]

 

REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VVLMIN]

 

REAL

Constant

Enter a value for the minimum limit [pu].

 

PSS4C: Power System Stabilizer Data: Low Frequency BandPSS4C: Power System Stabilizer Data: Low Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS4C is selected.

Gain in Positive Branch [KL1]


REAL

Constant

Enter a value for the gain in positive branch [pu].

Proportional Gain in First Block [KL11]


REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TL1]


REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TL2]


REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TL3]


REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TL4]


REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TL5]


REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TL6]


REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Negative Branch [KL2]


REAL

Constant

Enter a value for the gain in negative branch [pu].

Proportional Gain in First Block [KL17]


REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TL7]


REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TL8]


REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TL9]


REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TL10]


REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TL11]


REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TL12]


REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Common Branch [KL]


REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VLMAX]


REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VLMIN]


REAL

Constant

Enter a value for the minimum limit [pu].

 

PSS4C: Power System Stabilizer Data: Intermediate Frequency BandPSS4C: Power System Stabilizer Data: Intermediate Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS4C is selected.

Gain in Positive Branch [KI1]

 

REAL

Constant

Enter a value for the gain in positive branch [pu].

Proportional Gain in First Block [KI11]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TI1]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TI2]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TI3]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TI4]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TI5]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TI6]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Negative Branch [KI2]

 

REAL

Constant

Enter a value for the gain in negative branch [pu].

Proportional Gain in First Block [KI17]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TI7]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TI8]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TI9]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TI10]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TI11]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TI12]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Common Branch [KI]

 

REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VIMAX]

 

REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VIMIN]

 

REAL

Constant

Enter a value for the minimum limit [pu].

 

PSS4C: Power System Stabilizer Data: High Frequency BandPSS4C: Power System Stabilizer Data: High Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS4C is selected.

Gain in Positive Branch [KH1]

 

REAL

Constant

Enter a value for the gain in positive branch [pu].

Proportional Gain in First Block [KH11]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TH1]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TH2]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TH3]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TH4]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TH5]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TH6]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Negative Branch [KH2]

 

REAL

Constant

Enter a value for the gain in negative branch [pu].

Proportional Gain in First Block [KH17]

 

REAL

Constant

Enter a value for the proportional gain in first block [pu].

Derivative Time Constant in First Block [TH7]

 

REAL

Constant

Enter a value for the derivative time constant in first block [s].

Lag Time Constant in First Block [TH8]

 

REAL

Constant

Enter a value for the lag time constant in first block [s].

Lead Time Constant in Second Block [TH9]

 

REAL

Constant

Enter a value for the lead time constant in second block [s].

Lag Time Constant in Second Block [TH10]

 

REAL

Constant

Enter a value for the lag time constant in second block [s].

Lead Time Constant in Third Block [TH11]

 

REAL

Constant

Enter a value for the lead time constant in third block [s].

Lag Time Constant in Third Block [TH12]

 

REAL

Constant

Enter a value for the lag time constant in third block [s].

Gain in Common Branch [KH]

 

REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VHMAX]

 

REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VHMIN]

 

REAL

Constant

Enter a value for the minimum limit [pu].

 

PSS5C: Power System Stabilizer Data: Common DataPSS5C: Power System Stabilizer Data: Common Data

NOTE:  This category is enabled only when Stabilizer? | PSS5C is selected.

PSS Output Maximum Limit [VSTMAX]


REAL

Constant

Enter a value for the PSS output maximum limit [pu].

PSS Output Minimum Limit [VSTMIN]


REAL

Constant

Enter a value for the PSS output minimum limit [pu].

 

PSS5C: Power System Stabilizer Data: Very Low Frequency BandPSS5C: Power System Stabilizer Data: Very Low Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS5C is selected.

Central Frequency (in Hz) [FVL]


REAL

Constant

Enter a value for the central frequency [Hz].

Gain in Common Branch [KVL]


REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VVLMAX]


REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VVLMIN]


REAL

Constant

Enter a value for the minimum limit [pu].

 

PSS5C: Power System Stabilizer Data: Low Frequency BandPSS5C: Power System Stabilizer Data: Low Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS5C is selected.

Central Frequency (in Hz) [FL]


REAL

Constant

Enter a value for the central frequency [Hz].

Gain in Common Branch [KL]


REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VLMAX]


REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VLMIN]


REAL

Constant

Enter a value for the minimum limit [pu].


 

PSS5C: Power System Stabilizer Data: Intermediate Frequency BandPSS5C: Power System Stabilizer Data: Intermediate Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS5C is selected.

Central Frequency (in Hz) [FI]


REAL

Constant

Enter a value for the central frequency [Hz].

Gain in Common Branch [KI]


REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VIMAX]


REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VIMIN]


REAL

Constant

Enter a value for the minimum limit [pu].


 

PSS5C: Power System Stabilizer Data: High Frequency BandPSS5C: Power System Stabilizer Data: High Frequency Band

NOTE:  This category is enabled only when Stabilizer? | PSS5C is selected.

Central Frequency (in Hz) [FH]


REAL

Constant

Enter a value for the central frequency [Hz].

Gain in Common Branch [KH]


REAL

Constant

Enter a value for the gain in common branch [pu].

Maximum Limit [VHMAX]


REAL

Constant

Enter a value for the maximum limit [pu].

Minimum Limit [VHMIN]


REAL

Constant

Enter a value for the minimum limit [pu].


 

PSS6C: PSS Signal DataPSS6C: PSS Signal Data

NOTE:  This category is enabled only when Stabilizer? | PSS6C is selected.

 First Input Signal

 

Choice

 

Select None, Frequency, Speed or Power.

 

 

 

 

 

First Signal Maximum Input [VSI1MAX]

 

REAL

Constant

Enter a value for the first signal maximum input [pu].

 

 

 

 

 

First Signal Minimum Input [VSI1MIN]

 

REAL

Constant

Enter a value for the first signal minimum input [pu].

 

 

 

 

 

1st Signal Transducer Time Constant [T1]

 

REAL

Constant

Enter a value for the first signal transducer time constant [s].

 

 

 

 

 

1st Signal Gain [Ks1]

 

REAL

Constant

Enter a value for the first signal gain [pu].

 

 

 

 

 

1st Signal Time Constant [T3]

 

REAL

Constant

Enter a value for the first signal time constant [s].

 

 

 

 

 

Second Input Signal

 

Choice

 

Select None, Frequency, Speed or Power.

 

 

 

 

 

Second Signal Maximum Input [VSI2MAX]

 

REAL

Constant

Enter a value for the second signal maximum input [pu].

 

 

 

 

 

Second Signal Minimum Input [VSI2MIN]

 

REAL

Constant

Enter a value for the second signal minimum input [pu].

 

 

 

 

 

2nd Signal Transducer Time Constant [T2]

 

REAL

Constant

Enter a value for the second signal transducer time constant [s].

 

 

 

 

 

2nd Signal Gain [Ks2]

 

REAL

Constant

Enter a value for the second signal gain [pu].

 

 

 

 

 

2nd Signal Washout Time Constant [Macc]

 

REAL

Constant

Enter a value for the second signal washout time constant [s].

 

 

 

 

 

2nd Signal 2nd Time Constant [T4]

 

REAL

Constant

Enter a value for the second signal second time constant [s].

 

PSS6C: Power System Stabilizer Data: Common PathPSS6C: Power System Stabilizer Data: Common Path

NOTE:  This category is enabled only when Stabilizer? | PSS6C is selected.

Washout Time Constant [TD]


REAL

Constant

Enter a value for the washout time constant [s].

Canonical Gain 0 [K0]


REAL

Constant

Enter a value for the canonical gain 0 [pu].

1st Block Time Constant [Ti1]


REAL

Constant

Enter a value for the first block time constant [s].

Canonical Gain 1 [K1]


REAL

Constant

Enter a value for the canonical gain 1 [pu].

2nd Block Time Constant [Ti2]


REAL

Constant

Enter a value for the second block time constant [s].

Canonical Gain 2 [K2]


REAL

Constant

Enter a value for the canonical gain 2 [pu].

Include 3rd Block?


Choice


Select from Yes or No.

3rd Block Time Constant [Ti3]


REAL

Constant

Enter a value for the third block time constant [s].


This value is available only when Include 3rd Block? | Yes is selected.

Canonical Gain 3 [K3]


REAL

Constant

Enter a value for the canonical gain 3 [pu].


This value is available only when Include 3rd Block? | Yes is selected.

Include 4th Block?


Choice


Select from Yes or No.


This value is available only when Include 3rd Block? | Yes is selected.

4th Block Time Constant [Ti4]


REAL

Constant

Enter a value for the fourth block time constant [s].


This value is available only when Include 4th Block? | Yes is selected.

Canonical Gain 4 [K4]


REAL

Constant

Enter a value for the canonical gain 4 [pu].


This value is available only when Include 4th Block? | Yes is selected.

PSS Main Gain [KS]


REAL

Constant

Enter a value for the PSS main gain [pu].

PSS Output Maximum Limit [VSTMAX]


REAL

Constant

Enter a value for the PSS output maximum limit [pu].

PSS Output Minimum Limit [VSTMIN]


REAL

Constant

Enter a value for the PSS output minimum limit [pu]..

PSS Output Logic - Upper Threshold for Power Output [PPSON]


REAL

Constant

Enter a value for the PSS output logic - upper threshold for power output [pu].

PSS Output Logic - Lower Threshold for Power Output [PPSOFF]


REAL

Constant

Enter a value for the PSS output logic - lower threshold for power output [pu].

 

PSS7C: PSS Signal DataPSS7C: PSS Signal Data

NOTE:  This category is enabled only when Stabilizer? | PSS7C is selected.

 First Input Signal


Choice


Select None, Frequency, Speed or Power.






First Signal Maximum Input [VSI1MAX]


REAL

Constant

Enter a value for the first signal maximum input [pu].






First Signal Minimum Input [VSI1MIN]


REAL

Constant

Enter a value for the first signal minimum input [pu].






1st Signal 1st Washout Time Constant [TW1]


REAL

Constant

Enter a value for the first signal first washout time constant [s].






1st Signal 2nd Washout Time Constant [TW2]


REAL

Constant

Enter a value for the first signal second washout time constant [s].






1st Signal Transducer Time Constant [T6]


REAL

Constant

Enter a value for the first signal transducer time constant [s].






Second Input Signal


Choice


Select None, Frequency, Speed or Power.






Second Signal Maximum Input [VSI2MAX]


REAL

Constant

Enter a value for the second signal maximum input [pu].






Second Signal Minimum Input [VSI2MIN]


REAL

Constant

Enter a value for the second signal minimum input [pu].






2nd Signal 1st Washout Time Constant [TW3]


REAL

Constant

Enter a value for the second signal first washout time constant [s].






2nd Signal 2nd Washout Time Constant [TW4]


REAL

Constant

Enter a value for the second signal second washout time constant [s].






2nd Signal Gain [Ks2]


REAL

Constant

Enter a value for the second signal gain [pu].






2nd Signal Transducer Time Constant [T7]


REAL

Constant

Enter a value for the second signal transducer time constant [s].






2nd Signal 2nd Gain [Ks3]


REAL

Constant

Enter a value for the second signal second gain [pu].

 

PSS7C: PSS Lead-Lag DataPSS7C: PSS Lead-Lag Data

NOTE:  This category is enabled only when Stabilizer? | PSS7C is selected.

 Filter Lead Time Constant [T8]

 

REAL

Constant

Enter a value for the filter lead time constant [s].

Filter Lag Time Constant [T9]

 

REAL

Constant

Enter a value for the filter lag time constant [s].

Integer Filter Constant [N]

 

INTEGER

Constant

Enter a value for the integer filter constant.

Integer Filter Constant [M]

 

INTEGER

Constant

Enter a value for the integer filter constant.

 

PSS7C: Power System Stabilizer Data: Common PathPSS7C: Power System Stabilizer Data: Common Path

NOTE:  This category is enabled only when Stabilizer? | PSS7C is selected.

PSS Gain [Ks1]

 

REAL

Constant

Enter a value for the PSS gain [pu].

Canonical Gain 0 [K0]

 

REAL

Constant

Enter a value for the canonical gain 0 [pu].

1st Block Time Constant [Ti1]

 

REAL

Constant

Enter a value for the first block time constant [s].

Canonical Gain 1 [K1]

 

REAL

Constant

Enter a value for the canonical gain 1 [pu].

2nd Block Time Constant [Ti2]

 

REAL

Constant

Enter a value for the second block time constant [s].

Canonical Gain 2 [K2]

 

REAL

Constant

Enter a value for the canonical gain 2 [pu].

Include 3rd Block?

 

Choice

 

Select from Yes or No.

3rd Block Time Constant [Ti3]

 

REAL

Constant

Enter a value for the third block time constant [s].

 

This value is available only when Include 3rd Block? | Yes is selected.

Canonical Gain 3 [K3]

 

REAL

Constant

Enter a value for the canonical gain 3 [pu].

 

This value is available only when Include 3rd Block? | Yes is selected.

Include 4th Block?

 

Choice

 

Select from Yes or No.

 

This value is available only when Include 3rd Block? | Yes is selected.

4th Block Time Constant [Ti4]

 

REAL

Constant

Enter a value for the fourth block time constant [s].

 

This value is available only when Include 4th Block? | Yes is selected.

Canonical Gain 4 [K4]

 

REAL

Constant

Enter a value for the canonical gain 4 [pu].

 

This value is available only when Include 4th Block? | Yes is selected.

PSS Output Maximum Limit [VSTMAX]

 

REAL

Constant

Enter a value for the PSS output maximum limit [pu].

PSS Output Minimum Limit [VSTMIN]

 

REAL

Constant

Enter a value for the PSS output minimum limit [pu]..

PSS Output Logic - Upper Threshold for Power Output [PPSON]

 

REAL

Constant

Enter a value for the PSS output logic - upper threshold for power output [pu].

PSS Output Logic - Lower Threshold for Power Output [PPSOFF]

 

REAL

Constant

Enter a value for the PSS output logic - lower threshold for power output [pu].

 

DEC1A: Discontinuous Excitation Controller Data : Section 1DEC1A: Discontinuous Excitation Controller Data : Section 1

NOTE:  This category is enabled only when Discontinuous Excitation Controller? | DEC1A is selected.

 DEC Washout Time Constant [Tw5]

 

REAL

Constant

Enter a value for the DEC washout time constant [s].

Terminal Voltage Level Reference [VTC]

 

REAL

Constant

Enter a value for the terminal voltage level reference [pu].

Regulator Voltage Reference [VAL]

 

REAL

Constant

Enter a value for the regulator voltage reference [pu].

Speed Change Reference [Esc]

 

REAL

Constant

Enter a value for the speed change reference [pu].

Terminal Voltage Reference [VTLMT]

 

REAL

Constant

Enter a value for the terminal voltage reference [pu].

Terminal Voltage Maximum Deviation Over Reference

 

REAL

Constant

Enter a value for the terminal voltage maximum deviation over reference [pu].

Terminal Voltage Minimum Deviation Over Reference

 

REAL

Constant

Enter a value for the terminal voltage minimum deviation over reference [pu].

Terminal Voltage Limiter gain [KETL]

 

REAL

Constant

Enter a value for the terminal voltage limiter gain [pu].

Voltage Limiter Lead Time Constant [TL1]

 

REAL

Constant

Enter a value for the terminal voltage limiter lead time constant [s].

Voltage Limiter Lag Time Constant [TL2]

 

REAL

Constant

Enter a value for the terminal voltage limiter lag time constant [s].

 

DEC1A: Discontinuous Excitation Controller DataDEC1A: Discontinuous Excitation Controller Data

NOTE:  This category is enabled only when Discontinuous Excitation Controller? | DEC1A is selected.

 Bang-Bang Controller Maximum Limit [VTM]

 

REAL

Constant

Enter a value for the bang-bang controller maximum limit [pu].

Bang-Bang Controller Minimum Limit [VTN]

 

REAL

Constant

Enter a value for the bang-bang controller minimum limit [pu].

Reset Delay Time [TD]

 

REAL

Constant

Enter a value for the reset delay time [s].

Integrator Gain [KAN]

 

REAL

Constant

Enter a value for the integrator gain [pu].

Integrator Time Constant [TAN]

 

REAL

Constant

Enter a value for the integrator time constant [s].

Integrator Maximum Limit [VANMAX]

 

REAL

Constant

Enter a value for the integrator maximum limit [pu].

PSS plus DEC Maximum Limit [VSMAX]

 

REAL

Constant

Enter a value for the PSS plus DEC maximum limit [pu].

PSS plus DEC Minimum Limit [VSMIN]

 

REAL

Constant

Enter a value for the PSS plus PSS and DEC minimum limit [pu].

 

DEC2A: Discontinuous Excitation Controller DataDEC2A: Discontinuous Excitation Controller Data

NOTE:  This category is enabled only when Discontinuous Excitation Controller? | DEC2A is selected.

 Trigger Signal Amplitude [Vk]

 

REAL

Constant

Enter a value for the trigger signal amplitude [pu].

Controller Time Constant [TD1]

 

REAL

Constant

Enter a value for the controller time constant [s].

DEC Washout Time Constant [TD2]

 

REAL

Constant

Enter a value for the DEC washout time constant [s].

Terminal Voltage Maximum Limit [VTLIMIT]

 

REAL

Constant

Enter a value for the terminal voltage maximum limit [pu].

DEC Maximum Limit

 

REAL

Constant

Enter a value for the DEC maximum limit [pu].

DEC Minimum Limit

 

REAL

Constant

Enter a value for the DEC minimum limit [pu].

 

DEC3A: Discontinuous Excitation Controller DataDEC3A: Discontinuous Excitation Controller Data

NOTE: This category is enabled only when Discontinuous Excitation Controller? | DEC3A is selected.

Controller Input Reference [VTMIN]

 

REAL

Constant

Enter a value for the controller input reference [pu].

Reset Time Delay [TDR]

 

REAL

Constant

Enter a value for the reset time delay [s].