Traces¶
Trace¶
-
class
mhi.enerplot.Trace(initializer=None, domain=None)¶ A trace is an array of numbers which hold the value of a signal as it changes over some domain. For instance, a trace may contain a voltage value as it changes over time.
ChannelsandCurvesboth extend from theTraceclass.-
increasing()¶ Test if a trace contains strictly increasing values.
A strictly increase trace is suitable to use as the domain of a dataset.
Returns: Trueif every value is larger than the previous one.Return type: bool
-
decreasing()¶ Test if a trace contains strictly decreasing values.
Returns: Trueif every value is smaller than the previous one.Return type: bool
-
Basic Operations¶
Many basic operations are already possible on a Trace.
All operations return a new trace; the original trace is unmodified.
Given a trace a the following unary operations exist:
| Operators | Operation |
|---|---|
len(a) |
Number of data points in the trace |
a[n] |
Access the n-th data point in the trace |
-a |
Negation |
abs(a) |
Absolute value |
math.ceil(a) |
Values rounded up to an integer |
math.floor(a) |
Values rounded down to an integer |
math.trunc(a) |
Values truncate towards zero |
Given two traces, a and b, or a trace and a scalar number
in either order, the following operations exist:
| Operators | Operation |
|---|---|
a + b |
Addition |
a - b |
Subtraction |
a * b |
Multiplication |
a / b |
Division |
a ** b |
Exponentiation |
Note
If an operation is performed on two traces of different lengths, these operations will the result in a trace which matches the length of the shorter of the two traces. The extra data in the longer trace is ignored.
Convolution¶
Given two traces, a and b, the operation a @ b returns
a convolution of the two traces.
For example, the given the Finite Impulse Response of a transfer function, the output signal can be created by convolving the input with the finite impulse response:
fir = mhi.enerplot.Trace([0.75, 1.0, 0.5, 0.25, 0.125])
output = input @ fir
The length of the output is 1 sample less than the sum of the lengths of the two input traces.
Other Operations¶
Additional operations on traces require importing methods from the
mhi.enerplot.math library.
Example:
The following computed trace would approximate the full wave rectifier output:
from mhi.enerplot.math import minimum, maximum cigre = enerplot.datafile('Cigre_47.csv') a = cigre[r'Rectifier\AC Voltage:1'] b = cigre[r'Rectifier\AC Voltage:2'] c = cigre[r'Rectifier\AC Voltage:3'] rectifier_out = maximum(a, b, c) - minimum(a, b, c)
Logarthimic¶
-
mhi.enerplot.math.exp(trace)¶ Return a new trace where every value is transformed as: x → e^x.
-
mhi.enerplot.math.ln(trace)¶ Return a new trace where every value is transformed as: x → logₑ(x).
All values less than or equal to zero are replaced with
NaN
-
mhi.enerplot.math.log(trace, base=2.718281828459045)¶ Return a new trace where every value is transformed as: x → logₐ(x). The default base is “e”, for the natural logarithm.
All values less than or equal to zero are transformed to
NaN
-
mhi.enerplot.math.log10(trace)¶ Return a new trace where every value is transformed as: x → log₁₀(x).
All values less than or equal to zero are transformed to
NaN
-
mhi.enerplot.math.sqrt(trace)¶ Return a new trace where every value is transformed as: x → √x.
All values less than or equal to zero are transformed to
NaN
Circular¶
-
mhi.enerplot.math.degrees(trace)¶ Return a new trace where every value is transformed from radians to degrees.
-
mhi.enerplot.math.radians(trace)¶ Return a new trace where every value is transformed from degrees to radians.
-
mhi.enerplot.math.sin(trace)¶ Return a new trace where every value is transformed as: x → sin(x).
The input to the sin(x) function is intrepeted as being in radians.
-
mhi.enerplot.math.cos(trace)¶ Return a new trace where every value is transformed as: x → cos(x).
The input to the sin(x) function is intrepeted as being in radians.
-
mhi.enerplot.math.tan(trace)¶ Return a new trace where every value is transformed as: x → tan(x).
The input to the sin(x) function is intrepeted as being in radians.
-
mhi.enerplot.math.asin(trace)¶ Return a new trace where every value is transformed as: x → sin⁻¹(x).
The output of the sin⁻¹(x) function is in radians.
NaNis returned for all values greater than 1, or less than -1.
-
mhi.enerplot.math.acos(trace)¶ Return a new trace where every value is transformed as: x → cos⁻¹(x).
The output of the cos⁻¹(x) function is in radians.
NaNis returned for all values greater than 1, or less than -1.
-
mhi.enerplot.math.atan(trace)¶ Return a new trace where every value is transformed as: x → tan⁻¹(x).
The output of the tan⁻¹(x) function is in radians.
-
mhi.enerplot.math.hypot(x, y)¶ Compute a new trace, returning the Euclidean distance, sqrt(x*x + y*y), for each pair of values from the two input traces.
The follow two statements produce equivalent output:
from mhi.enerplot.math import hypot, sqrt c = hypot(a, b) c = sqrt(a ** 2 + b ** 2)
The first statement is significantly faster since the second statement requires allocating several temporary traces for holding the intermediate results.
-
mhi.enerplot.math.atan2(y, x)¶ Compute a new trace, returning the arc tangent (measured in radians) of y/x, for each pair of values from the two input traces. Unlike atan(y/x), the signs of both x and y are considered.
When used in conjunction with the
hypot(), two traces representing real and imaginary values may be converted into two traces representing polar coordinates: magnitude and angle.
Selection¶
-
mhi.enerplot.math.maximum(*traces)¶ Return a new trace where the maximum value from each trace, at each point, is selected.
-
mhi.enerplot.math.minimum(*traces)¶ Return a new trace where the minimum value from each trace, at each point, is selected.
Processing¶
-
mhi.enerplot.math.smooth(trace, time_constant, domain)¶ Return a smoothed version of the input trace.
This function simulates a lag or ‘real pole’ function. The time domain solution algorithm is based on the trapezoidal rule. The solution method for this function is as follows:
Parameters: - trace (Trace) – the input to be smoothed.
- time_constant (float) – the time-constant to be used for smoothing
- domain (float or trace) – the time-step, or the signal domain
Examples
If
inputrepresents aCurvefrom aDataFilewith a 50µs timestep, the following statements would produce the same output:from mhi.enerplot.math import smooth output = smooth(input, 0.001, 50e-6) output = smooth(input, 0.001, input.domain)