Arrestor I-V Characteristic Data

 

The arrestor I-V characteristic data can be supplied to the model by the following means:

Defaut Characteristics (ASEA XAP-A)

To use the arrestor default characteristics, ensure that is I-V Characteristic | Default is selected.  The default characteristics approximate the ASEA XAP-A metal oxide surge arrester.  The ASEA XAP-A characteristics are given below for reference:

 

 

I

V

0.001

1.100

0.01

1.600

0.1

1.700

0.2

1.739

0.38

1.777

0.65

1.815

1.11

1.853

1.50

1.881

2.00

1.910

2.80

1.948

200.0

3.200

 

 

Note that the voltage is in per unit, and so the Arrester Voltage Rating input parameter should be the rated voltage in kV.

Entering Data from an External File

If entering the I-V coordinates from an external data file, a certain structured format must be followed.  Descriptive comments cannot be used.   The last data point must be followed by a '/'.  A maximum of 100 data points is allowed.  Also, an 'ENDFILE:' statement must be placed at the end of the file.

 

An example data file is given below:

 

 

0.001 1.1

0.01  1.6

0.1   1.7 /

ENDFILE:

 

 