
This component simulates the dynamics of up to 26 masses connected to a single rotating shaft. One mass is normally used to represent the generator, and the electrical torque Te is applied to it. One mass may be used to represent an exciter. The remaining masses represent turbines, and the mechanical torque Tm is divided among them. The resulting speed of the generator Wpu or Wrad is then output, for use as input to the interfaced machine model.
More: |
For Use With... |
|
Choice |
|
Select Synchronous Machine, Induction Machine, DC Machine or PM Machine. |
|
|
|
|
|
Number of Turbines |
|
INTEGER |
Literal |
Enter the number of turbines (1 to 25). If 25 turbines are desired, the exciter mass cannot be modeled. |
|
|
|
|
|
Model Exciter Mass |
|
Choice |
|
Select Yes or No. If 5 turbines are desired, the exciter mass cannot be modeled |
|
|
|
|
|
Machine Total MVA |
|
REAL |
Constant |
The 3-phase MVA of the machine, to which the multi-mass is attached [MVA] |
|
|
|
|
|
Electrical Base Frequency |
|
REAL |
Constant |
Enter electrical base frequency [Hz] |
|
|
|
|
|
Machine Mechanical Synchronous Speed |
|
REAL |
Constant |
Actual speed of the machine [rpm] |
|
|
|
|
|
Machine Initial Electrical Speed |
|
REAL |
Constant |
Initial speed of the machine [pu] |
|
|
|
|
|
Unit System Number (see help) |
|
Choice |
|
Select 1 to 10. See the table below for definitions |
|
|
|
|
|
Initialization switch: 0-Init;1-Release |
|
INTEGER |
Variable |
0-Initialization, 1-Release. Until the switch turns 1 the generator will be spinning at the 'Machine rated speed' or at rated slip. The variable name can come from the one assigned in the synchronous machine under the Output Variables for Controller Initialization section of the input parameters. |
System of Units Table
Unit System |
Inertia Constant Ji or Hi |
Mutual Damping MDij |
Spring Constant Kij |
Torque Share TFi |
Self Damping SDi |
1 |
lb•ft•ft |
- |
lbf•ft/rad |
pu |
- |
2 |
in•lbf•s2 |
- |
lbf•in/rad |
pu |
- |
3 |
lb•in•in |
- |
lbf•in/rad |
pu |
- |
4 |
H [s] |
- |
pu |
pu |
- |
5 |
kg•m•m |
- |
N•m/rad |
pu |
- |
6 |
lb•ft•ft |
lbf•ft•s/rad |
lbf•ft/rad |
pu |
lbf•ft•s/rad |
7 |
in•lbf•s2 |
lbf•in•s/rad |
lbf•in/rad |
pu |
lbf•in•s/rad |
8 |
lb•in•in |
lbf•in•s/rad |
lbf•in/rad |
pu |
lbf•in•s/rad |
9 |
H [s] |
pu |
pu |
pu |
pu |
10 |
kg•m•m |
N•m•s/rad |
N•m/rad |
pu |
N•m•s/rad |
Output Initialized Mechanical Torque |
|
Choice |
|
Select Yes or No. This input could be used to initialize the governor/turbine and is available only if the For Use With... input parameter is set to Synchronous Machine |
|
|
|
|
|
Input Initialized Steady Electrical Torque |
|
Choice |
|
Select Yes or No. If the steady state Electrical Torque is available, this could be used to initialize the multi-mass and is available only if the For Use With... input parameter is set to Synchronous Machine. |
NOTE: The inertia constants must be entered in the units specified in the Unit System Number input parameter
Turbine # Inertia Constant |
|
REAL |
Constant |
Enter the inertia constant for the corresponding turbine |
NOTE: The spring constants must be entered in the units specified in the Unit System Number input parameter
Spring Constant From Turbine # to # |
|
REAL |
Constant |
The shaft spring constants are used to describe the dynamics of the shaft. The torque exerted on the adjacent masses by the shaft is proportional to the relative mechanical angles between those masses. |
Torque Share for Turbine # |
|
REAL |
Constant |
The total mechanical torque applied to the multi-mass system may be distributed over the turbine masses. Each turbine receives a fraction of the total mechanical torque: Its torque share. The sum of the torque shares for all turbines modeled must total 1 (one) [pu] |
Modal Damping for all Modes |
|
REAL |
Constant |
A uniform modal damping factor for all modes. This input is used only for Unit System Numbers 1 to 5. The time constant for the decay of all modal oscillations is inverse of this [1/s] |
NOTE: The damping constants must be entered in the units specified in the Unit System Number input parameter
Turbine # Self Damping |
|
REAL |
Constant |
The self-damping coefficient creates a torque on the appropriate mass which is proportional to the speed of the mass. This may be used to represent friction and windage for the mass. |
NOTE: The damping constants must be entered in the units specified in the Unit System Number input parameter
Damping Between Turbine # & # |
|
REAL |
Constant |
The mutual damping coefficient creates a torque, which is proportional to the difference in speed from one mass to the next. Thus, this torque will not be applied in steady state, but will damp out oscillations between masses. |
Generator Inertia Constant |
|
REAL |
Constant |
Enter the inertia constant for the generator |
|
|
|
|
|
Exciter Inertia Constant |
|
REAL |
Constant |
Enter the inertia constant for the generator exciter |
|
|
|
|
|
Spring Constant from the Last Turbine to Generator |
|
REAL |
Constant |
Spring constant for the shaft between the generator and the turbine connected to it. |
|
|
|
|
|
Spring Constant from Generator to Exciter |
|
REAL |
Constant |
Spring constant for the shaft connecting the generator to the excitor. |
|
|
|
|
|
Generator Self Damping |
|
REAL |
Constant |
The self-damping coefficient creates a torque on the appropriate mass which is proportional to the speed of the mass. This may be used to represent friction and windage for the mass. |
|
|
|
|
|
Exciter Self Damping |
|
REAL |
Constant |
The self-damping coefficient creates a torque on the appropriate mass which is proportional to the speed of the mass. This may be used to represent friction and windage for the mass. |
|
|
|
|
|
Damping Between Last Turbine and Generator |
|
REAL |
Constant |
The mutual damping coefficient creates a torque, which is proportional to the difference in speed from one mass to the next. Thus, this torque will not be applied in steady state, but will damp out oscillations between masses. |
|
|
|
|
|
Damping Between Generator and Exciter |
|
REAL |
Constant |
The mutual damping coefficient creates a torque, which is proportional to the difference in speed from one mass to the next. Thus, this torque will not be applied in steady state, but will damp out oscillations between masses. |
Internal Output Variable Names - 1
Torque on Shaft from Mass # - # |
|
REAL |
Output |
Torque experienced by the shaft # [pu]. |
Internal Output Variable Names - 2
Mechanical Position of Mass # Relative to Generator |
|
REAL |
Output |
Mechanical position of mass # with respect to the generator [rad]. |
Internal Output Variable Names - 3
Rated Mechanical Speed of the system |
|
REAL |
Output |
Rated mechanical speed [rad/s]. |
|
|
|
|
|
Delta Mechanical Speed of Mass # |
|
REAL |
Output |
Difference between the rated speed and the speed of mass # [rad/s]. |