Current Transformer - Lucas Model

 

Description

This component models a current transformer connected to an inductive burden (relay).  The input to the model is the measured primary line current (in kA).  The model calculates the secondary current from the CT winding (in Amps).

 

More:

Finding Saturation Constants And Indices To Match Magnetising Characteristics

Loss Characteristics (Lucas Model)

PSCAD Reference [12]

Input Parameters

Main DataMain Data

 

 Name for Identification

 

Text

 

Optional text parameter for identification of the component.

         

 Primary Turns

 

INTEGER

Constant

Enter the number of turns in the primary winding

 

 

 

 

 

Secondary Turns

 

INTEGER

Constant

Enter the number of turns in the secondary winding

 

 

 

 

 

Secondary Resistance

 

REAL

Constant

Enter the secondary winding resistance [W]

 

 

 

 

 

Secondary Inductance

 

REAL

Constant

Enter the leakage inductance of the CT referred to the secondary winding [H]

 

 

 

 

 

Area

 

REAL

Constant

Enter the mean core cross section [m2]

 

 

 

 

 

Path Length

 

REAL

Constant

Enter the mean path length of the core [m]

 

 

 

 

 

Frequency

 

REAL

Constant

Enter the rated frequency [Hz]

 

 

 

 

 

Remnant Flux Density

 

REAL

Constant

Enter the remnant flux density of the core at time zero [T]

 

 

 

 

 

Initial Current in Core

 

REAL

Constant

Enter the initial current in the magnetizing branch of the core at time zero (if any) [A]

 

 

 

 

 

Magnetic Material

 

Choice

 

Select Custom or Silectron 53.  If custom is selected, the core material data must be entered by the user

 

Saturation CharacteristicsSaturation Characteristics

NOTE:  These parameters are enabled only if Magnetic Material is selected as Custom.

 

 Flux Density at Knee Point

 

REAL

Constant

Flux density at the knee point of the B-H curve [T]

 

 

 

 

 

Constant #

 

REAL

Constant

Enter the corresponding constant Ki.  See Finding Saturation Constants And Indices To Match Magnetising Characteristics  for more details

 

 

 

 

 

Index #

 

INTEGER

Constant

Enter the corresponding index ai.  See Finding Saturation Constants And Indices To Match Magnetising Characteristics  for more details

 

Loss CharacteristicsLoss Characteristics

NOTE:  These parameters are enabled only if Magnetic Material is selected as Custom.  See Loss Characteristics (Lucas Model) for a more complete description of loss coefficients.

 

 Eddy Current Loss Coefficient

 

REAL

Constant

Enter the eddy current loss coefficient Ged.

 

 

 

 

 

Hysteresis Loss Coefficient #

 

REAL

Constant

Enter the values for hysteresis loss coefficients Gi.

 

The default values are for the Silectron 53 material.  If you have the B-H data for a different material and want to compute the coefficients and indices for saturation and hysteresis loss, please contact the PSCAD Support Desk (support@mhi.ca).  There is no fixed method to find G-constants for hysteresis loss.

 

BurdenBurden

 

Burden Resistance

 

REAL

Constant

Enter the value of the burden (relay) resistance [W]

 

 

 

 

 

Burden Inductance

 

REAL

Constant

Enter the value of the burden (relay) inductance [H]

 

Internal Output VariablesInternal Output Variables

 

Ideal CT Output Current

 

REAL

Output

Secondary current if the CT was 'ideal' [A]

 

 

 

 

 

Total Core Current

 

REAL

Output

This is the sum of the core loss current and the magnetizing current [A]

 

 

 

 

 

Magnetizing Current

 

REAL

Output

Enter a name for the CT magnetizing current [A]

 

 

 

 

 

Flux Density

 

REAL

Output

Enter a name for the flux density of the core [T]