The RTP/COMTRADE Recorder component can record up to a total of 28 simulated data signals. The user can store the recorded data in one of three standard formats:
RTP (Real Time Playback)
COMTRADE 91
COMTRADE 99
Although designed especially for seamless use with the Real Time Playback (RTP) relay testing equipment, it may also be used for convenient recording in both COMTRADE 91 and COMTRADE 99 formats.
External Recording Channels:
A1, A2,...,A12: Analog input channels
D1, D2,...,D16: Digital input channels
Although all 28 inputs channels accept real variables, Analog and Digital inputs are treated slightly different for the purpose of RTP and COMTRADE compatibility.
Recording Control:
Start: Adjustable recording start time [s].
End: Adjustable recording end time [s].
Start and End inputs are provided for control of a specified recording interval. Normally, a simple constant value may be attached to these inputs, however more complicated systems may be used to vary these times during a multiple run simulation. Typical usage is to connect two sliders to these pins and adjust start and stop times in a control panel.
More: |
Main ConfigurationMain Configuration
Name for Identification |
Text |
Optional text parameter for identification of the component. |
||
Output File Name |
|
Text |
|
Enter the output file name with no extension. The length of the file name is limited to 8 characters for MS-DOS/ COMTRADE compatibility. Appropriate extension(s) will be automatically appended |
|
|
|
|
|
Output File Format |
|
Choice |
|
Select RTP, COMTRADE 91 or COMTRADE 99 output formats |
|
|
|
|
|
Recording Time Step (microseconds) |
|
INTEGER |
Literal |
Enter the recording time step. If this value is less than the simulation time step, the simulation time step will be used instead. If the recording time step is greater than the simulation time step, interpolation is used for synchronization between the two [ms] |
|
|
|
|
|
Low pass Filtering Enable |
|
Choice |
|
Select Rstep > Tstep to enable low pass filtering of input signals when Recording Time Step is greater than the simulation time step |
|
|
|
|
|
System Frequency |
|
Choice |
|
The fundamental system frequency. Select 50 Hz or 60 Hz |
|
|
|
|
|
Station Name |
|
Text |
|
Enter a descriptive station name. This parameter is required for COMTRADE output files only |
|
|
|
|
|
Recorder Device Number |
|
INTEGER |
Literal |
Enter a number from 1 to 99. This parameter allows EMTDC to distinguish between multiple recorders used in the same simulation. If this is the case, then each recorder must be assigned a unique device number |
|
|
|
|
|
Number of 16-bit Analog Channels |
|
INTEGER |
Literal |
Enter the number of 'analog' input channels to be recorded (12 maximum) |
|
|
|
|
|
Number of Digital Channels |
|
INTEGER |
Literal |
Enter the number of 'digital' input channels to be recorded (16 maximum) |
|
|
|
|
|
Output files |
|
Choice |
|
Select Single or Multiple. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected. The COMTRADE specification permits large output files to be split into smaller files suitable for transfer between computers via 1.44MB floppy disks |
|
|
|
|
|
Number of Extra Header File Lines |
|
INTEGER |
Literal |
Select the number of lines to be added to the COMTRADE header file (5 maximum). The text is entered via the COMTRADE Header File Dialog. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
Analog Output Minimum |
|
INTEGER |
Literal |
For uni-polar integer representation of the captured data, enter 0. For bipolar representation, enter the appropriate value (ex. -4096). This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
Analog Output Maximum |
|
INTEGER |
Literal |
For uni-polar integer representation of the captured data, enter the appropriate non-zero value. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
Capture Trigger Time |
|
Choice |
|
Select Yes or No. |
COMTRADE Header FileCOMTRADE Header File
Extra Header File Line # |
|
Text |
|
The user can enter descriptive text desired in these lines. This parameter is used only if Number of Extra Header File Lines is non-zero |
Analog ChannelsAnalog Channels
Analog Variable Name |
|
Text |
|
Enter the 'analog' input variable name. It should be less than 15 characters in length with no spaces between characters. This name is displayed in the legend window in the RTP Playback software preview window |
|
|
|
|
|
Variable Description (COMTRADE) |
|
Text |
|
Enter the variable description to be used in the COMTRADE configuration file. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
Variable Source |
|
Choice |
|
Select Primary or Secondary source. This parameter accounts for the CT/PT ratio. If Secondary is selected, then the value at the recorder input is passed directly to the output file. If Primary is selected, then the value at the recorder input is divided by the CT/PT ratio. The value sent to the recorder output file is always the secondary level |
|
|
|
|
|
Variable Type |
|
Choice |
|
Select Voltage, Current or Other. This information is required by the Playback and COMTRADE files to display the proper units. The RTP Playback program will automatically produce waveform displays based on units. If Other is selected then ASCII text can be added to describe the units for Other, and no scaling occurs. |
|
|
|
|
|
"Other" Unit |
|
Text |
|
The user can enter whatever units are appropriate for the enabled channels |
|
|
|
|
|
Phase Identification |
|
Choice |
|
Select phases A, B, C, or N. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
PT or CT Ratio |
|
REAL |
Literal |
Enter the PT or CT ratio for each variable. Remember that in PSCAD, the default primary values are in kV or kA |
|
|
|
|
|
Component Being Monitored (COMTRADE) |
|
Text |
|
Describe the component that is being monitored as required by the COMTRADE configuration file. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
Digital ChannelsDigital Channels
Status Variable Name |
|
Text |
|
Enter the 'digital' input variable name. It should be less than 15 characters in length with no spaces between characters. This name is displayed in the legend window in the RTP Playback software preview window. |
|
|
|
|
|
Variable Description |
|
Text |
|
Enter the variable description to be used in the COMTRADE configuration file. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |
|
|
|
|
|
Normal Operating State |
|
Choice |
|
Select 0 or 1. This information is required by the COMTRADE configuration file and is used to assign a default initial value to digital signals. This parameter is used only if Output File Format | COMTRADE 91 or COMTRADE 99 is selected |