This component models a hysteresis reactor. It can be connected to a single-phase or 3-phase node.
More: |
Base MVA per Phase |
REAL |
Constant |
Apparent power of the reactor per phase [MVA]. |
|
Base Operation Frequency |
REAL |
Constant |
[Hz]. |
|
Eddy Current Losses |
INTEGER |
Constant |
Eddy current loss portion of the total core losses based on MVA entered [pu]. |
|
Base Voltage Across the Reactor |
REAL |
Constant |
Enter the RMS voltage rating across the reactor [kV]. |
NOTE: See Transformer Magnetic Hysteresis for more details on these inputs
Hysteresis |
|
Choice |
|
Select Basic Model, or Jiles-Atherton.
The Basic Model models hysteresis based a translation on the transformer l-I characteristic, whereas the Jiles-Atherton model involves a conversion from an M-H loop to a B-H loop characteristic. |
|
|
|
|
|
Air Core Reactance |
|
REAL |
Constant |
Enter based on the base impedance [pu]. |
|
|
|
|
|
Remanent Flux |
REAL |
Constant |
Enter the remanent flux as a per-unit value of the peak flux at rated voltage [pu]. | |
|
|
|
|
|
Magnetizing Current |
REAL |
Constant |
Enter as a percentage of the base current [%]. |
|
|
|
|
|
|
Loop Width |
REAL |
Constant |
Enter as a percentage of the Magnetizing Current [%]. | |
|
|
|
|
|
Knee Voltage |
REAL |
Constant |
The knee point voltage corresponding to the knee point of the saturation curve [pu]. |
|
|
|
|
|
|
Nominal Flux Density |
REAL |
Constant |
Enter the nominal flux density corresponding to the saturation curve [T]. | |
Magnetic Material |
Choice |
Select custom material, or default. |
Magnetic Characteristics of the Material
NOTE: This category is enabled only if Hysteresis | Jiles-Atherton and Magnetic Material | custom material is selected.
Domain Flexing Parameter |
|
REAL |
Constant |
This parameter represents the contribution of reversible magnetization process. |
|
|
|
|
|
Domain Pinning Parameter |
|
REAL |
Constant |
This parameter has a direct impact on the width of the loop [A/m]. |
|
|
|
|
|
Parameter to Adjust K with M |
|
REAL |
Constant |
This parameter adjusts the domain pinning parameter with magnetization for better representation of the shoulder area. |
|
|
|
|
|
Inter-Domain Coupling |
|
REAL |
Constant |
|
|
|
|
|
|
Saturated Anhysteretic Magnetization |
|
REAL |
Constant |
[A/m]. |
|
|
|
|
|
Coefficient # of Anysteretic Curve |
|
REAL |
Constant |
|
Name for Magnetizing Current [kA] |
|
REAL |
Output |
Name for the magnetizing current [kA]. |
|
|
|
|
|
Name for Flux Linkage [kWb-N] |
|
REAL |
Output |
Name for the calculated flux linkage [kWb-N]. |
|
|
|
|
|
Name for Magnetic Field Intensity |
REAL |
Output |
Name for the magnetic field intensity.
This output is enabled only when Hysteresis | Jiles-Atherton is selected. |
|
|
|
|
|
|
Name for Flux Density [T] |
REAL |
Output |
Name for the flux density [T]. |