1-Phase 2-Winding UMEC Transformer

 

Description

This component models a 1-phase, 2-winding transformer and is based on the UMEC modelling approach.

 

Options are provided so that the user may model the core saturation characteristic directly as an I-V curve.  If desired, the magnetising branch can be eliminated altogether, leaving the transformer in 'ideal' mode, where all that remains is a series leakage reactance. Some elements of core geometry (i.e. core type, yoke and winding limb dimensions, etc.) are required for data input as well.

 

More:

The UMEC Approach

Input Parameters

ConfigurationConfiguration

 

 Transformer Name

 

Text

 

Just an identifier. A name should be entered here to avoid compilation warnings

 

 

 

 

 

Transformer MVA

 

REAL

Constant

The apparent power rating of the transformer [MVA]

 

 

 

 

 

Primary Voltage (RMS)

 

REAL

Constant

The voltage rating of the primary winding [kV]

 

 

 

 

 

Secondary Voltage (RMS)

 

REAL

Constant

The voltage rating of the secondary winding [kV]

 

 

 

 

 

Base Operation Frequency

 

REAL

Constant

The base frequency of the electrical system, in which the transformer resides [Hz]

 

 

 

 

 

Leakage Reactance

 

REAL

Constant

The total leakage reactance of transformer. This can be calculated based on short-circuit test results [pu]

 

 

 

 

 

Copper Losses

 

REAL

Literal

Enter the total copper losses for the transformer. Equivalent winding resistances are calculated based on this entry so that losses are distributed evenly among all the windings. These resistances are then placed in series with the windings [pu]

 

 

 

 

 

Model Saturation?

 

Choice

 

Select Yes or No to include core saturation in the model.

NOTE: Even if this parameter is set as Yes, saturation still needs to be enabled using the Enable Saturation parameter in the Saturation Curve category.

 

 

 

 

 

Tap Changer on Winding

 

Choice

 

Select the winding number on which to place the on-line tap changer (or none)

 

 

 

 

 

Graphics Display

 

Choice

 

Select Windings or Circles

 

Tap SettingTap Setting

 

 Tap Setting

 

REAL

Constant

Select the tap setting. This parameter cannot be adjusted during the run

 

 

Saturation CurveSaturation Curve

NOTE:  The I-V characteristic defined by these inputs construct a piecewise linear saturation curve, where transitions between points are fully interpolated by PSCAD.  If a 0.0 value is entered, PSCAD will ignore all points following the 0.0. This is useful in instances where the saturation curve has less then 10 points.  The UMEC algorithm requires that the first quadrant of the saturation curve (with V in the vertical axis and I in the horizontal axis) to decrease in slope with each subsequent segment of the spline curve. Points that lead to slopes bigger that the previous registered slope will be ignored until a point leads to a smaller slope.

 

 Magnetizing Current at Rated Voltage

 

REAL

Constant

The magnetizing current at rated voltage. This parameter is only used if core saturation is disabled [%]

 

 

 

 

 

Enable Saturation

 

REAL

Variable

Enter 0 to disable and 1 to enable core saturation.

 

NOTE: The parameter Model Saturation? in the Configuration category must be enabled in order to use this parameter.

 

 

 

 

 

RMS Data Conversion

 

Choice

 

Select Legacy or Enhanced. 

 

Legacy would give the old conversion method used, whereas Enhanced gives the new method with a better match.

 

 

 

 

 

Point # – Current as a Percentage

 

REAL

Constant

Enter the I-coordinates of the I-V curve. These points can be non-zero if desired. The maximum number of points is 10 [%]

 

 

 

 

 

Point # – Voltage in pu

 

REAL

Constant

Enter the V-coordinates of the I-V curve. These points can be non-zero if desired. The maximum number of points is 10 [pu]

 

 

Core Aspect RatiosCore Aspect Ratios

 

 Ratio Yoke/Winding-Limb Length

 

REAL

Constant

Enter the ratio of core yoke length to the core winding-limb length

 

 

 

 

 

Ratio Yoke/Winding-Limb Area

 

REAL

Constant

Enter the ratio of core yoke area to the core winding-limb area

 

 

Monitoring of Winding CurrentsMonitoring of Winding Currents

 

 Name for Winding # Current

 

REAL

Output

Name for the specified winding current [kA]

 

Transformer Flux (pu)Transformer Flux (pu)

 

 Winding # Flux

 

REAL

Output

Name for the flux in the specified core winding-limb [pu]

 

 

 

 

 

Winding # Leakage Flux

 

REAL

Output

Name for the leakage flux in the specified core winding-limb [pu]

 

 

 

 

 

Yoke Flux

 

REAL

Output

Name for the flux in the core yoke [pu]