Single-Phase Current Source

 

Description

This component models a single-phase, ideal AC or DC current source.

 

There are two types of input control methods, Internal and External:

This model is a direct representation of the EMTDC CCIN current injection.

 

More:

Three-Phase Current Source

Node Based (GGIN) Electric Interface

Input Parameters

ConfigurationConfiguration

 

 Source Name

 

Text

 

Just an identifier. A name should be entered here to avoid compilation warnings

 

 

 

 

 

External Control?

 

Choice

 

Select Yes or No

 

Signal ParametersSignal Parameters

NOTE: These parameters are used only if External Control? | No is selected.

 Mag (AC:L-G, RMS DC:Pk)

 

REAL

Constant

For an AC source, enter the line-to-ground, RMS source current. For DC, enter the peak current [kA]

 

 

 

 

 

Frequency (0 for DC)

 

REAL

Constant

Source frequency (enter 0.0 for DC) [Hz]

 

 

 

 

 

Initial Phase

 

REAL

Constant

Initial source phase shift [°]

 

 

 

 

 

Ramp Up Time

 

REAL

Constant

Enter a time for the source to ramp up to 1.0 pu.

 

Use a minimum ramp up time of 3 times the fundamental frequency period (i.e. 0.05 s for 60 Hz and 0.06 s for 50 Hz) in most cases to reduce start-up transients [s]