Hysteresis Reactor

 

Description

This component models a hysteresis reactor. It can be connected to a single-phase or 3-phase node.

 

More:

The Classical Approach

Adjusting Saturation Properties

Transformer Magnetic Hysteresis

Input Parameters

ConfigurationConfiguration

 

Base MVA per Phase

 

REAL

Constant

Apparent power of the reactor per phase [MVA].

         

Base Operation Frequency

 

REAL

Constant

[Hz].

         

Eddy Current Losses

 

INTEGER

Constant

Eddy current loss portion of the total core losses based on MVA entered [pu].

         

Base Voltage Across the Reactor

 

REAL

Constant

Enter the RMS voltage rating across the reactor [kV].

 

SaturationSaturation

NOTE: See Transformer Magnetic Hysteresis for more details on these inputs

 

Hysteresis

 

Choice

 

Select Basic Model, or Jiles-Atherton.

 

The Basic Model models hysteresis based a translation on the transformer l-I characteristic, whereas the Jiles-Atherton model involves a conversion from an M-H loop to a B-H loop characteristic.

 

 

 

 

 

Air Core Reactance

 

REAL

Constant

Enter based on the base impedance [pu].

 

 

 

 

 

Remanent Flux

 

REAL

Constant

Enter the remanent flux as a per-unit value of the peak flux at rated voltage [pu].

 

 

 

 

 

Magnetizing Current

 

REAL

Constant

Enter as a percentage of the base current [%].

 

 

 

 

 

Loop Width

 

REAL

Constant

Enter as a percentage of the Magnetizing Current [%].

 

 

 

 

 

Knee Voltage

 

REAL

Constant

The knee point voltage corresponding to the knee point of the saturation curve [pu].

 

 

 

 

 

Nominal Flux Density

 

REAL

Constant

Enter the nominal flux density corresponding to the saturation curve [T].
         

Magnetic Material

 

Choice

 

Select custom material, or default.

 

 

Magnetic Characteristics of the MaterialMagnetic Characteristics of the Material

NOTE: This category is enabled only if Hysteresis | Jiles-Atherton  and Magnetic Material | custom material is selected.

 

 Domain Flexing Parameter

 

REAL

Constant

This parameter represents the contribution of reversible magnetization process.

 

 

 

 

 

Domain Pinning Parameter

 

REAL

Constant

This parameter has a direct impact on the width of the loop [A/m].

 

 

 

 

 

Parameter to Adjust K with M

 

REAL

Constant

This parameter adjusts the domain pinning parameter with magnetization for better representation of the shoulder area.

 

 

 

 

 

Inter-Domain Coupling

 

REAL

Constant

 

 

 

 

 

 

Saturated Anhysteretic Magnetization

 

REAL

Constant

[A/m].

 

 

 

 

 

Coefficient # of Anysteretic Curve

 

REAL

Constant

 

 

 

Internal OutputsInternal Outputs

 

Name for Magnetizing Current [kA]

 

REAL

Output

Name for the magnetizing current [kA].

 

 

 

 

 

Name for Flux Linkage [kWb-N]

 

REAL

Output

Name for the calculated flux linkage [kWb-N].

 

 

 

 

 

Name for Magnetic Field Intensity

 

REAL

Output

Name for the magnetic field intensity.

 

This output is enabled only when Hysteresis | Jiles-Atherton is selected.

 

 

 

 

 

Name for Flux Density [T]

 

REAL

Output

Name for the flux density [T].