Fixed Load (1 and 3-Phase, LG)

Description

This component models the load characteristics as a function of voltage magnitude and frequency. The expression of the characteristics is as follows:

 

 

And,

 

 

Where,

 

P =

Equivalent load real power

Q =

Equivalent load reactive power

Scale =

Load scaling factor

P0 =

Real power at specified condition (Rated or Initial terminal)

Q0 =

Reactive power at specified condition (Rated or Initial terminal)

Load voltage

Voltage at specified condition (Rated or Initial terminal)

KPF =

dP/dF  Frequency index for real power

KQF =

dQ/dF  Frequency index for reactive power

KA =

Portion of the load specified by the first term

NPA =

dP/dV voltage index for real power in the first term

NQA =

dQ/dV voltage index for reactive power in the first term

KB =

Portion of the load specified by the second term

NPB =

dP/dV voltage index for real power in the second term

NQB =

dQ/dV voltage index for reactive power in the second term

KC =

Portion of the load specified by the third term

NPC =

dP/dV voltage index for real power in the third term

NQC =

dQ/dV voltage index for reactive power in the third term

NOTE: dQ, dP, dV and dF are in all per-unit quantities

If this component is used in single-phase mode, every half cycle (at the appropriate voltage zero), the shunt resistor/inductor/capacitor is updated to reflect the nonlinear load effect as a function of RMS voltage and frequency.  

 

If used in a 3-phase, single-line mode, the RLC values of all phases are changed when the voltage of any one of the phases goes through a zero crossing.

 

The load remains in constant impedance form until the user specified number of cycles of the fundamental frequency is passed.  The nonlinear characteristic is effective within ±20% of the specified RMS voltage and ±DF% of the rated frequency (DF is defined as minimum of 10, 90/KPF and 90/KQF).  Outside this range, the load reverts to constant impedance.

 

Quick Reference for Index Parameter Selection

 

dP/dV

dQ/dV

dP/dF

dQ/dF

Constant Resistance

 2

 

0

 

Constant Reactance

 

2

 

0

Constant Inductance

 

2

 

-1

Constant Capacitance

 

2

 

1

Constant Real Current

1

 

0

 

Constant Reactive Current

 

1

 

0

Constant Real Power

0

 

0

 

Constant Reactive Power

 

0

 

0

 

IMPORTANT NOTE: The initial values of R, L and C are computed based on the rated conditions supplied by the user. These values are kept constant until the specified number of cycles of the fundamental frequency has passed.

 

More:

Fixed Load (1-Phase, L-L)

See Reference [3] for more details on static load models and typical values for NP, NQ, KPF and KQF.

Input Parameters

ConfigurationConfiguration

 

 Name

 

Text

 

Optional text parameter for identification of the component.

         

  Rated Real Power per Phase

 

REAL

Constant

Real steady-state 1-phase power into load [MW].

 

 

 

 

 

Rated Reactive Power (+inductive) per Phase

 

REAL

Constant

Steady state reactive power into load, where inductive load is entered as +ve in value (capacitive as -ve) [MVAr].

 

 

 

 

 

Rated Load Voltage (RMS L-G)

 

REAL

Constant

Expected steady state line-to-ground RMS volts across the load [kV].

 

 

 

 

 

Initial Terminal Voltage

 

REAL

Constant

Initial terminal voltage [pu].

 

 

 

 

 

PQ Defined at

 

Choice

 

Select Rated Voltage or Initial Terminal Voltage.

 

 

 

 

 

Number of Parts in the Composite Load

 

Choice

 

Select 1, 2 or 3.

 

 

 

 

 

Fundamental Frequency

 

REAL

Constant

System fundamental frequency [Hz].

 

 

 

 

 

Scaling Factor

 

REAL

Variable

Enter a scaling factor for the load. Scaling factor should be positive.

 

 

 

 

 

Number of Cycles before Load Release

 

REAL

Constant

Enter the number of cycles of the rated frequency during which time load is held constant.

 

 

 

 

 

Display Details?

 

Choice

 

Select Yes or No.

 

Selecting Yes will display Rated Real Power per Phase and Rated Reactive Power on the component graphic.

 

 

 

 

 

Frequency Index for P (dP/dF)

 

REAL

Constant

Frequency index for real power.

         

Frequency Index for Q (dQ/dF)

 

REAL

Constant

Frequency index for reactive power.

 

 

 

 

 

Voltage Index for P (dP/dV) - Part A

 

REAL

Constant

Voltage index for real power.

 

 

 

 

 

Voltage Index for Q (dQ/dV) - Part A

 

REAL

Constant

Voltage index for reactive power.

 

Internal OutputsInternal Outputs

 

  Effective Resistance per Phase

 

REAL

Output

Name for effective per phase resistance [W].

 

 

 

 

 

Effective Inductance per Phase

 

REAL

Output

Name for effective per phase inductance [H].

 

 

 

 

 

Effective Capacitance per Phase

 

REAL

Output

Name for effective per phase capacitance [mF].